MEC16-03119
| Final | 10/25/2016 | 10/25/2016 | 10/25/2016 4:17:47 PM | P | PASS |
|
|
Please call Arthur, thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
MEC16-04709
| Final | 10/25/2016 | 10/25/2016 | 10/25/2016 3:34:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Arcadio Martinez
|
MEC15-02510
| Mec-Aging Inspection | 10/25/2016 | 10/25/2016 | 10/25/2016 3:17:21 PM | | CANC |
|
|
|
MEC16-04637
| Rough-in | 10/25/2016 | 10/25/2016 | 10/25/2016 2:46:22 PM | P | FAIL |
|
|
light test for grease duct for final connection - call travis Phone #: ###-#### Inspection requested via web by Brandon Sorensen - Called Travis, no answer. I left a message but haven't heard back. I went by job site and no one was there. Need to reschedule
|
MEC16-04628
| Pressure Test | 10/25/2016 | 10/25/2016 | 10/25/2016 2:04:22 PM | P | PART |
|
|
please call Ted, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - 20lb gas pass. Need to wrap gas pipe where it passes through exterior wall with inert material.
|
MEC16-04628
| Rough-in | 10/25/2016 | 10/25/2016 | 10/25/2016 2:03:40 PM | P | FAIL |
|
|
please call Ted, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum - Need approved manual J on site, Need to complete crawl prior to rough in inspection, need to rough in fresh air to return plenum, Need to wrap gas pipe where it passes through exterior wall with inert material.
|
MEC16-03990
| Final | 10/19/2016 | 10/25/2016 | 10/25/2016 1:51:55 PM | P | CANC |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 3:30 PM . Contact for Right Now is Mary ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|
MEC11-02664
| Mec-Aging Inspection | 10/25/2016 | 10/25/2016 | 10/25/2016 1:38:30 PM | | CANC |
|
|
|
MEC16-01618
| Final | 10/25/2016 | 10/25/2016 | 10/25/2016 1:27:15 PM | P | PART |
|
|
2nd floor Inspection requested via web by william kerwin - all of 3rd floor units okay, 2nd floor units okay except for units 201, 205, 209 that the condensates are not complete in.
|
MEC16-01284
| Final | 10/25/2016 | 10/25/2016 | 10/25/2016 1:26:52 PM | P | PART |
|
|
2nd floor Inspection requested via web by william kerwin - all of 3rd floor units okay, 2nd floor units okay except for units 201, 205, 209 that the condensates are not complete in.
|
MEC16-04725
| Final | 10/24/2016 | 10/25/2016 | 10/25/2016 9:28:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee
|
MEC16-04383
| Final | 10/24/2016 | 10/25/2016 | 10/25/2016 8:48:07 AM | A | PART |
|
|
8:30 final. Hiod balance is done and report will be in hand. Phone #: ###-#### Inspection requested via web by Drew Tverdy - Temporary occupancy okay. Missing gas piping to MUA, Missing water to evap on MUA, Water heater flu needs to be 10' away, or 3' above fresh air intake. need equipment set under hood. Need structrual supports for roof top equipment per approved plans
|
MEC16-04672
| Final | 10/24/2016 | 10/25/2016 | 10/24/2016 9:42:26 AM | P | CANC |
|
|
Installer Cody ###-#### Thank you Phone #: ###-#### >> Inspection requested via web by Dustin Rich Inspection cancelled from web by: Dustin Rich
|