ELE13-00542
| ELE-Aging Inspection | 10/25/2017 | 10/25/2017 | 10/27/2017 2:15:16 PM | | FAIL |
|
|
still waiting on contractor to schedule final
|
ELE13-03325
| ELE-Aging Inspection | 10/25/2017 | 10/25/2017 | 10/26/2017 8:02:32 AM | | PASS |
|
|
see final inspection
|
ELE17-02598
| Final | 10/25/2017 | 10/25/2017 | 10/25/2017 2:02:38 PM | P | PASS |
|
|
Michael Phone #: ###-####...ok to final
|
ELE17-03309
| Final | 10/25/2017 | 10/25/2017 | 10/25/2017 1:17:39 PM | P | PASS |
|
|
Roy Phone #: ###-####...ceiling grid ok to cover and job complete ok to final
|
ELE17-03144
| Rough-In Permanent Service | 10/25/2017 | 10/25/2017 | 10/25/2017 12:43:54 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tracy Robertson...rough ok to cover...p/s u/g n ok
|
ELE17-03289
| Final | 10/24/2017 | 10/25/2017 | 10/25/2017 10:33:52 AM | A | CANC |
|
|
Please call 30 minutes in advance. Phone #: ###-#### Inspection requested via web by Larry Stevens...not ready at this time
|
ELE17-03289
| Permanent Service | 10/25/2017 | 10/25/2017 | 10/25/2017 10:33:21 AM | A | PASS |
|
|
Please call 30 minutes in advance. Phone #: ###-#### Inspection requested via web by Larry Stevens...p/s u/g new ok
|
ELE17-03491
| Rough-In Permanent Service | 10/24/2017 | 10/25/2017 | 10/25/2017 10:04:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe...rough ok to cover...p/s u/g new ok
|
ELE17-00675
| Final | 10/24/2017 | 10/25/2017 | 10/25/2017 9:33:06 AM | A | FAIL |
|
|
access 6021 Phone #: ###-#### Inspection requested via web by David Nelson... 1) listed cover used to hook up water htr-110.3B 2) downstairs bedroom lights not working-110.7 3) exposed wires in down stairs bed light-110.7 4) downstairs closet light to close to shelf-410.16(C) 5) open can trims in master closet-410.16(B) 6) hood has no power-110.7 7) microwave circuit needs breaker lock out 8) GFI in garage shall be firmly attached to box-406.5
|
ELE13-00903
| ELE-Aging Inspection | 10/25/2017 | 10/25/2017 | 10/25/2017 8:28:14 AM | | DONE |
|
|
see final
|
ELE13-00903
| Final | 10/25/2017 | 10/25/2017 | 10/25/2017 8:07:09 AM | A | PASS |
|
|
closing permit...no work was done under this permit...homeowner decided not to do job
|