Inspections for the day of: Wednesday, October 25, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04280 FIRE-Final Inspection10/23/201710/25/201710/25/2017 1:41:04 PMPCANC
Inspection request cancelled per conversation with point of contact, Noah Phone #: ###-####. Inspection will be rescheduled for a later date.
FIR17-00473 INSP-Sprinkler Rough-in10/25/201710/25/201710/25/2017 1:40:19 PMPPART
Partial rough to cover inspection complete for level 2, notated city approved plans with green highlighter/red ink areas inspected today and approved for cover.
BLD17-02903 FIRE-Final Inspection10/24/201710/25/201710/25/2017 10:16:06 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher will be mounted in discussed location. Final life fire safety inspection passed/complete.
FIR17-00608 INSP-Final Inspection10/25/201710/25/201710/25/2017 9:35:20 AMPPASS
Final fire sprinkler inspection for area of work passed/complete.
FIR17-00618 INSP-Final Inspection10/24/201710/25/201710/25/2017 9:34:45 AMACANC
John Phone #: ###-####, wrong permit requested by contractor, this request is cancelled.
FIR17-00473 INSP-Sprinkler Rough-in10/25/201710/25/201710/25/2017 9:20:33 AMPCANC
Mark Jensen is the contact for this inspection. Thank you. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
BLD16-01060 FIRE-Final Inspection10/25/201710/25/201710/25/2017 9:13:47 AMAPASS
Life fire safety inspection complete for pool area, life fire safety inspection passed/complete for Building 3
FIR16-00586 INSP-Sprinkler Rough-in10/24/201710/25/201710/25/2017 9:12:35 AMAFAIL
Overhead fire sprinkler piping is covered in numerous areas, a clear pocket must be maintained between sheetrock and fire sprinkler piping for radiant heat to reach pipe. Overehad fire sprinkler piping north of the e;evator lobby is not approved for cover.