ELE18-04011
| Electrical Rough-In | 10/25/2018 | 10/25/2018 | 10/25/2018 2:34:27 PM | P | PASS |
|
|
Re-inspection please Phone #: ###-#### Inspection requested via web by Winters LLC
Correction fixed ceiling only ok to cover
|
ELE18-01777
| Conference | 10/25/2018 | 10/25/2018 | 10/25/2018 2:33:19 PM | P | DONE |
|
|
Please call 45 minutes prior to arrival ###-#### John E Phone #: ###-#### Inspection requested via web by John Edwards Discussed place,ment of panel ion moc-up kithcen area in dispal room. Panerl will be cut in on back side to maintian 36" of clearence and will case through to feed branch circuit, If any questions please call Eric ###-####
|
ELE18-04115
| Permanent Service | 10/24/2018 | 10/25/2018 | 10/25/2018 12:02:36 PM | A | FAIL |
|
|
Service inspection Phone #: ###-#### Inspection requested via web by Matthew White250 Main bonding jumper required
|
ELE18-03323
| Final | 10/24/2018 | 10/25/2018 | 10/25/2018 11:35:21 AM | A | PASS |
|
|
final on shop Phone #: ###-#### Inspection requested via web by Brian Hughes Final for detached shop only ok
|
ELE18-03059
| Final | 10/24/2018 | 10/25/2018 | 10/25/2018 11:10:27 AM | A | PASS |
|
|
access 4888 Phone #: ###-#### Inspection requested via web by David Nelson Correction fixed final ok
|
ELE18-03912
| Electrical Rough-In | 10/23/2018 | 10/25/2018 | 10/25/2018 11:09:53 AM | A | PASS |
|
|
Jordan Hill Phone #: ###-#### Inspection requested via web by Ashley Lanham Verified listing and scope of Solar Array install
|
ELE18-04007
| Electrical Rough-In | 10/24/2018 | 10/25/2018 | 10/25/2018 11:00:59 AM | A | PASS |
|
|
Garage Code 2465 Phone #: ###-#### Inspection requested via web by Icon Electric Stern WARNING given to insulatipn compay for sealing proir to inspection and is aware of the issue and will not do this again.. Rough-in ok to cover
|
ELE18-04007
| Permanent Service | 10/25/2018 | 10/25/2018 | 10/25/2018 11:00:43 AM | P | PASS |
|
|
Garage Code 2465 Phone #: ###-#### Inspection requested via web by Icon Electric p/s u/g n ok
|
ELE18-04103
| Electrical Rough-In | 10/24/2018 | 10/25/2018 | 10/25/2018 10:00:07 AM | A | PASS |
|
|
listing inspection for solar equipment. The roof top crew will be there from for the whole a.m. Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King Verified U/L listing and scope of work on Solar Array
|
ELE18-03906
| Final | 10/24/2018 | 10/25/2018 | 10/25/2018 9:11:53 AM | A | PASS |
|
|
Robert Phone #: ###-#### Final ok
|