BLD00-02296
| FIRE-Alarm Testing | 10/24/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | CANC |
|
|
###-#### CHRISTOPHER duplicate inspection 10/26/2001 3:53:40 PM
|
BLD00-02694
| FIRE-Alarm Testing | 10/24/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | CANC |
|
|
wrong permit number, inspection was for fire alarm 10/26/2001 8:14:50 AM
|
FIR01-00350
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 8:07:48 AM Shell sprinkler system OK for sign off
|
BLD00-02631
| FIRE-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PART |
|
|
Added by Inspector: 430 On 10/26/2001 8:17:22 AM Buildings "A" and "B" fire alarm, fire sprinkler and life/safety has been inspected and is OK for perm. occ. Building "C" and "D" to be scheduled by contractor
|
FIR01-00362
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PART |
|
|
Added by Inspector: 430 On 10/26/2001 8:22:51 AM Building "A" and "B" OK for perm. occ. Contractor to schedule building "C" and "D"
|
FIR01-00287
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:34:39 AM Sprinkler system OK for perm occ
|
FIR01-00225
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:38:12 AM OK for perm occ
|
FIR01-00184
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:38:54 AM OK for perm. occ.
|
FIR01-00183
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:36:26 AM Underground OK for use
|
FIR01-00209
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:37:21 AM OK for perm occ.
|
FIR01-00185
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:39:28 AM OK for perm. occ.
|
FIR01-00239
| INSP-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | A | PASS |
|
|
Added by Inspector: 430 On 10/26/2001 10:40:06 AM OK for perm. occ.
|
BLD01-02767
| FIRE-Final Inspection | 10/26/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | P | FAIL |
|
|
Smoke detectors missing or not working 10/26/2001 3:54:17 PM
|
FIR01-00315
| INSP-Sprinkler Rough-in/Hydro | 10/25/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | P | CANC |
|
|
Approved plans not on site. Contractor to reschedule 10/26/2001 3:54:50 PM
|
FIR01-00293
| INSP-Sprinkler Rough-in/Hydro | 10/25/2001 | 10/26/2001 | 10/26/2001 12:00:00 AM | P | PASS |
|
|
Sprinkler rough-in OK 10/26/2001 3:55:35 PM
|