Inspections for the day of: Tuesday, October 26, 2004.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-02571 Conference10/25/200410/26/200410/26/2004 12:00:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer needs pool light listed boxes, and bond all pool cover metal 10/26/2004 10:26:47 AM
ELE04-02792 Permanent Service10/25/200410/26/200410/26/2004 12:00:00 AMANR
WE ARE READY FOR PERMANENT SEVICE FOR THIS PROJECT. IF YOU HAVE ANY QUESTIONS, PLEASE FEEL FREE TO CONTACT US AT THE OFFICE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called needs grds and bonds to p/s at out building, 250.32 10/26/2004 10:25:01 AM
ELE04-02903 Final10/25/200410/26/200410/26/2004 12:00:00 AMAPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 10/26/2004 8:28:28 AM
ELE04-02964 Final10/25/200410/26/200410/26/2004 12:00:00 AMACANC
dave- please call before you go out; Phone #: ###-#### Internet Inspection Request from: Jan Rice needs pm inspection 10/26/2004 10:25:28 AM
ELE03-04066 Final10/25/200410/26/200410/26/2004 12:00:00 AMAPASS
Mark; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok card signed 10/26/2004 12:02:09 PM
ELE04-02788 Conference10/25/200410/26/200410/26/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/25/2004 at 9:02:50 PM. Contact: ###-####. see added r/i 10/26/2004 1:35:26 PM
ELE04-02140 Electrical Rough-In10/26/200410/26/200410/26/2004 12:00:00 AMPPASS
amy please call before you go; Phone #: ###-#### Internet Inspection Request from: Jan Rice ok 10/26/2004 3:51:05 PM
ELE04-03271 Rough-In Permanent Service10/26/200410/26/200410/26/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 10/26/2004 at 8:30:19 AM. Contact: ###-####. r/i for walls and ceiling ok only cor. posted called B C C u/g covered before inspection, 250.24 GEC shall terminate to neutral not equip. grd bus , and ID meter space 10/26/2004 4:40:51 PM
ELE04-02651 Final10/26/200410/26/200410/26/2004 12:00:00 AMPNH
Terry- ###-#### call 1/2 hr ahead; Phone #: ###-#### Internet Inspection Request from: Jan Rice conference ok 10/26/2004 2:59:59 PM
ELE04-02964 Final10/26/200410/26/200410/26/2004 12:00:00 AMPPASS
ok see added p/s 10/26/2004 3:00:55 PM
ELE04-02788 Electrical Rough-In10/26/200410/26/200410/26/2004 12:00:00 AMPPART
ceiling borders ok, cor. posted 300.11 needs own support wires, and shall not support cables from raceways or cables, 358.28 over 4 90s in emt, 330.30 strap mc
ELE04-02964 Permanent Service10/26/200410/26/200410/26/2004 12:00:00 AMPPASS
p/s o/h rec. ok