Inspections for the day of: Wednesday, October 26, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03820 Electrical Rough-In10/26/200510/26/200510/26/2005 8:20:53 PMPCANC
Rough-in inspection for walls; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson told electricians that insulation would have to be removed to inspect work. Also told them that 1-siding was not to be done without approval
ELE05-01814 Conference10/26/200510/26/200510/26/2005 8:18:50 PMPDONE
please call 1/2hr before so I can meet you there. Thank You Jeremy; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook looked at service and will have to install new u/g since concrete was poured over tail
ELE05-02837 Final10/26/200510/26/200510/26/2005 3:50:44 PMPPASS
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
ELE05-03904 Electrical Rough-In10/26/200510/26/200510/26/2005 2:48:43 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson called contr left corr notice,BCC shall provide address and job id sticker,312.5 gec shall have abrasion protection, 250.68 gec shall be accessible,110.12(A) unused openings shall be closed, 300.4(A)(1) and (D) bored holes and nm cable shall be 1 1/4" from edge of framing member,110.12(C) there shall be no damaged cable
ELE05-03885 Temporary Service10/26/200510/26/200510/26/2005 2:33:08 PMPPASS
spencer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corr made, t/s u/g n ok
ELE05-03902 Rough-In Permanent Service10/26/200510/26/200510/26/2005 1:09:13 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called contr, left corr notice, 334.30 nm cable shall be stapled within 12" of box, 300.4(A)(1) edge of hole shall be 1 1/4" from edge of framing member, 725.55(A) class 2 cable shall not be run in same hole as line volt cables,BCC all make-up shall be done
ELE05-03331 Permanent Service10/25/200510/26/200510/26/2005 10:05:06 AMADONE
COMPLETED SURVEY IS U/G HOOK-UP OK?; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen already had meter, called contr
ELE05-03021 Final10/26/200510/26/200510/26/2005 9:59:55 AMAPASS
per Jim Schmer corrections made, listings ok, ok to final, no card to sign on job site for occupancy
ELE04-04020 Electrical Rough-In10/26/200510/26/200510/26/2005 9:57:19 AMACANC
ELE05-03888 Final10/25/200510/26/200510/26/2005 9:32:39 AMAPASS
PEDISTAL SERVICE IS LOCATED IN THE NORTH EAST CORNER OF THE PARKING LOT ON THE SCHOOL GROUNDS; Phone #: ###-#### Internet Inspection Request from: VERN CHITWOOD p/s u/g n ok
ELE05-03180 Final10/25/200510/26/200510/26/2005 8:16:59 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty corr done, signed occ card, ok to final
ELE04-04020 Final10/26/200510/26/200510/26/2005 12:00:00 AMAPART
lights in corridor need securing, trash compactor needs wired, heat pumps in corridors need wired, rest ok for part final