ELE05-03820
| Electrical Rough-In | 10/26/2005 | 10/26/2005 | 10/26/2005 8:20:53 PM | P | CANC |
|
|
Rough-in inspection for walls; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson told electricians that insulation would have to be removed to inspect work. Also told them that 1-siding was not to be done without approval
|
ELE05-01814
| Conference | 10/26/2005 | 10/26/2005 | 10/26/2005 8:18:50 PM | P | DONE |
|
|
please call 1/2hr before so I can meet you there. Thank You Jeremy; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook looked at service and will have to install new u/g since concrete was poured over tail
|
ELE05-02837
| Final | 10/26/2005 | 10/26/2005 | 10/26/2005 3:50:44 PM | P | PASS |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
ELE05-03904
| Electrical Rough-In | 10/26/2005 | 10/26/2005 | 10/26/2005 2:48:43 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Nicole Richardson called contr left corr notice,BCC shall provide address and job id sticker,312.5 gec shall have abrasion protection, 250.68 gec shall be accessible,110.12(A) unused openings shall be closed, 300.4(A)(1) and (D) bored holes and nm cable shall be 1 1/4" from edge of framing member,110.12(C) there shall be no damaged cable
|
ELE05-03885
| Temporary Service | 10/26/2005 | 10/26/2005 | 10/26/2005 2:33:08 PM | P | PASS |
|
|
spencer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corr made, t/s u/g n ok
|
ELE05-03902
| Rough-In Permanent Service | 10/26/2005 | 10/26/2005 | 10/26/2005 1:09:13 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called contr, left corr notice, 334.30 nm cable shall be stapled within 12" of box, 300.4(A)(1) edge of hole shall be 1 1/4" from edge of framing member, 725.55(A) class 2 cable shall not be run in same hole as line volt cables,BCC all make-up shall be done
|
ELE05-03331
| Permanent Service | 10/25/2005 | 10/26/2005 | 10/26/2005 10:05:06 AM | A | DONE |
|
|
COMPLETED SURVEY IS U/G HOOK-UP OK?; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen already had meter, called contr
|
ELE05-03021
| Final | 10/26/2005 | 10/26/2005 | 10/26/2005 9:59:55 AM | A | PASS |
|
|
per Jim Schmer corrections made, listings ok, ok to final, no card to sign on job site for occupancy
|
ELE04-04020
| Electrical Rough-In | 10/26/2005 | 10/26/2005 | 10/26/2005 9:57:19 AM | A | CANC |
|
|
|
ELE05-03888
| Final | 10/25/2005 | 10/26/2005 | 10/26/2005 9:32:39 AM | A | PASS |
|
|
PEDISTAL SERVICE IS LOCATED IN THE NORTH EAST CORNER OF THE PARKING LOT ON THE SCHOOL GROUNDS; Phone #: ###-#### Internet Inspection Request from: VERN CHITWOOD p/s u/g n ok
|
ELE05-03180
| Final | 10/25/2005 | 10/26/2005 | 10/26/2005 8:16:59 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Hardisty corr done, signed occ card, ok to final
|
ELE04-04020
| Final | 10/26/2005 | 10/26/2005 | 10/26/2005 12:00:00 AM | A | PART |
|
|
lights in corridor need securing, trash compactor needs wired, heat pumps in corridors need wired, rest ok for part final
|