Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00372 INSP-Sprinkler Rough-in/Hydro10/25/200510/26/200510/26/2005 4:20:14 PMPDEFR
Inspection to be completed tomorrow AM.
FIR05-00404 INSP-Sprinkler Rough-in10/25/200510/26/200510/26/2005 4:19:07 PMAFAIL
Install two missing DP at garages, provide hangers for two DP in south garage, provide sprinkler coverage under open space below stairs 2nd floor, provide adequate clearance for pipe in metal vent for fireplace 2nd floor, a head is required in the master closet 3rd floor as it exceeds 24 sq. ft., an inspection for insulation installation protection for cold cavity areas is required prior to final cover per note #35, be aware of possible light fixture obstructions in some locations.
FIR05-00422 INSP-Sprinkler Rough-in10/26/200510/26/200510/26/2005 2:27:22 PMPFAIL
One head at sauna room is blocked by an adjacent cabinet, no escutcheons are installed at this time, discussed head location in laundry room and kitchen.
BLD04-01323 FIRE-Final Inspection10/25/200510/26/200510/26/2005 12:11:21 PMPNR
Items on previous inspection correction notice dated 10/24 have not been completed at this time.
FIR05-00089 INSP-Sprinkler Rough-in/Hydro10/25/200510/26/200510/26/2005 12:08:23 PMAFAIL
Three items remain not completed on correction notice including to verify required flow/pressure at the roof standpipe (500gpm @ 100psi see note #35), area above the restrooms 2nd floor is lacking full sprinkler coverage-full height wall must be completed or provide uprights above this space, tenant demising walls for future tenants have disrupted shell sprinkler coverage in several areas.
FIR05-00382 INSP-Final Inspection10/25/200510/26/200510/26/2005 10:33:15 AMAPASS
One horn/strobe device was relocated for correct coverage while on site, sample tube incorrectly installed was repaired while on site, all other items tested satisfactory. Fire alarm finaled.
BLD05-00859 FIRE-Final Inspection10/25/200510/26/200510/26/2005 10:29:21 AMAFAIL
Provide identification for the fire extinguisher cabinets, repair main entry exit sign, provide tenant suite address, verify hardware at the main entry/exit doors when installed, patio door hardware is key operated on both sides.
FIR05-00413 INSP-Final Inspection10/25/200510/26/200510/26/2005 7:39:13 AMPCANC
this is grants cell. Could we please schedule it after 2:30 pm?; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
FIR05-00378 INSP-Final Inspection10/26/200510/26/200510/26/2005 12:00:00 AMAFAIL
Review notes were not available on site for inspection, escutcheons are missing in three locations