Inspections for the day of: Wednesday, October 26, 2005.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01575 BLD-Aging Inspection10/26/200510/26/200510/31/2005 12:32:22 PM NR
I spoke to the building owner Scott and notified him that I had left a notice that the affected areas as described in the open building permits and fire permits would be shutdown/closed for use if all permits were not finaled by 11/11/05. The notice was left with Diane at the front desk. I spoke to Scott over the phone. He was going to contact Odie with Steed and Jim Danes with DeBest.
BLD05-02318 FIRE-Final Inspection10/26/200510/26/200510/26/2005 4:14:28 PMPPART
A temporary occupancy was given until the fire alarm plans have been approved. Life safety ok to final when this happens.
FIR05-00614 INSP-Final Inspection10/26/200510/26/200510/26/2005 4:13:00 PMPPASS
Fire sprinklers finaled
FIR05-00635 INSP-Final Inspection10/25/200510/26/200510/26/2005 4:12:14 PMAFAIL
The resident rooms do not meet the minimum sound requirements and the a/vs in the entry ways exceed 15' from the walls. Entry ways may be considered rooms if Mary agrees but strobe candella is still lacking. Interconnection between new NAC and panel has been tested and passed. End of line voltage for both NAC circuits has been tested and passed. Sound levels in the common areas passed.
FIR05-00652 INSP-Final Inspection10/25/200510/26/200510/26/2005 11:13:56 AMAPASS
Fire sprinkler finaled
BLD05-01608 FIRE-Final Inspection10/25/200510/26/200510/26/2005 11:13:32 AMAFAIL
Project not ready for inspection. Duct detectors not wired up yet, exit signs not working, extinguishers not mounted.
BLD05-02154 FIRE-Final Inspection10/25/200510/26/200510/26/2005 11:11:19 AMAPASS
Life safety finaled
FIR05-00257 INSP-Final Inspection10/25/200510/26/200510/26/2005 11:09:40 AMAPART
Area B was inspected this morning. See city approved resubmitted plans for specific device locations that have been inspected and passed.