ELE06-03964
| Electrical Rough-In | 10/26/2006 | 10/26/2006 | 10/26/2006 3:56:25 PM | P | CANC |
|
|
SEAN SIVESIND - HE WILL BE @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail this is a public works street lights for new subdivision, called also shall not use ENT for direct burial called contr.
|
ELE06-03954
| Temporary Service | 10/26/2006 | 10/26/2006 | 10/26/2006 3:38:37 PM | P | PASS |
|
|
this is a reinspection, any questions please call Dan Wright; Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s u/g new ok
|
ELE06-01795
| Final | 10/26/2006 | 10/26/2006 | 10/26/2006 3:04:24 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams survey called 410.8 clearence NW upstairs bed rm closet, final ok
|
ELE06-03941
| Permanent Service | 10/26/2006 | 10/26/2006 | 10/26/2006 1:37:02 PM | P | PASS |
|
|
tom; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie needs to address subpanel someone put new sq D guts in a old ITE fuse enclosure, needs 4 rope to dryer p/s u/g new ok
|
ELE06-03974
| Temporary Service | 10/26/2006 | 10/26/2006 | 10/26/2006 1:03:05 PM | P | FAIL |
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called fee due, 312.5 needs plastic conn, for GEC at t/s, 110.12(C) clean all foreign materials from t/s leaves, mouse nest and droppings, and dirt
|
ELE06-03387
| Electrical Rough-In | 10/25/2006 | 10/26/2006 | 10/26/2006 11:08:57 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton all walls and inside soffit
|
ELE06-03958
| Electrical Rough-In | 10/25/2006 | 10/26/2006 | 10/26/2006 10:44:09 AM | A | FAIL |
|
|
(1)Ceiling cover in west dining area. (2)Entry to kitchen. ** RESTAURANT OPENS AT 11:00AM. PLEASE INSPECT BEFORE IT OPENS. Thank you!!***; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corr. called300.11(A) shall installsupport per NEC and structural, 410.67(C) all wiring to recess fixtures is branch circuit, 330.30(B), 348.30(A) secure MC and FMC within 12" of boxes and boxes at recess fixtures, 300.4*D) 11/4" for cables parallel to studs
|
ELE06-03897
| Final | 10/25/2006 | 10/26/2006 | 10/26/2006 10:09:18 AM | A | FAIL |
|
|
Please inspect before 11:00 am. Work performed Ray Hall.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz corr. called 250.104(A)(1) nstill needs to bond hot and cold
|
ELE06-03952
| Rough-In Permanent Service | 10/26/2006 | 10/26/2006 | 10/26/2006 9:37:31 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/26/2006 at 7:11:38 AM. Contact: ###-####. corr, called 300.4(A)(1)&(D) nail plates and 11/4" parallel inside outside edges same for low voltage contr, 334.30 staple cables within 12" at panel, 314.20 outside light box garage exit door shall be flush with siding, needs protection cables garage attic access 6ft
|
ELE06-03952
| Permanent Service | 10/26/2006 | 10/26/2006 | 10/26/2006 9:25:03 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/26/2006 at 7:11:38 AM. Contact: ###-####. r/i failed, p/s u/g new ok
|
ELE06-03939
| Rough-In Permanent Service | 10/24/2006 | 10/26/2006 | 10/26/2006 9:12:08 AM | A | PASS |
|
|
Glen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt r/i ok needs outlet back upstairs bed rm by closet called p/s u/g new ok
|
ELE06-03938
| Rough-In Permanent Service | 10/24/2006 | 10/26/2006 | 10/26/2006 9:10:53 AM | A | PASS |
|
|
Glen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt r/i ok needs outlet upstairs back upstairs bed rm by closet called, p/s u/g new ok
|
ELE06-02779
| ELE-Aging Inspection | 10/26/2006 | 10/26/2006 | 10/26/2006 7:50:05 AM | | CANC |
|
|
|
ELE06-03907
| Final | 10/26/2006 | 10/26/2006 | 10/26/2006 7:45:47 AM | A | PASS |
|
|
My cell number is ###-####, thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher
|