Inspections for the day of: Thursday, October 26, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03964 Electrical Rough-In10/26/200610/26/200610/26/2006 3:56:25 PMPCANC
SEAN SIVESIND - HE WILL BE @ JOBSITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail this is a public works street lights for new subdivision, called also shall not use ENT for direct burial called contr.
ELE06-03954 Temporary Service10/26/200610/26/200610/26/2006 3:38:37 PMPPASS
this is a reinspection, any questions please call Dan Wright; Phone #: ###-#### Internet Inspection Request from: Jeff Radford t/s u/g new ok
ELE06-01795 Final10/26/200610/26/200610/26/2006 3:04:24 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams survey called 410.8 clearence NW upstairs bed rm closet, final ok
ELE06-03941 Permanent Service10/26/200610/26/200610/26/2006 1:37:02 PMPPASS
tom; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie needs to address subpanel someone put new sq D guts in a old ITE fuse enclosure, needs 4 rope to dryer p/s u/g new ok
ELE06-03974 Temporary Service10/26/200610/26/200610/26/2006 1:03:05 PMPFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr. called fee due, 312.5 needs plastic conn, for GEC at t/s, 110.12(C) clean all foreign materials from t/s leaves, mouse nest and droppings, and dirt
ELE06-03387 Electrical Rough-In10/25/200610/26/200610/26/2006 11:08:57 AMAPART
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton all walls and inside soffit
ELE06-03958 Electrical Rough-In10/25/200610/26/200610/26/2006 10:44:09 AMAFAIL
(1)Ceiling cover in west dining area. (2)Entry to kitchen. ** RESTAURANT OPENS AT 11:00AM. PLEASE INSPECT BEFORE IT OPENS. Thank you!!***; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen corr. called300.11(A) shall installsupport per NEC and structural, 410.67(C) all wiring to recess fixtures is branch circuit, 330.30(B), 348.30(A) secure MC and FMC within 12" of boxes and boxes at recess fixtures, 300.4*D) 11/4" for cables parallel to studs
ELE06-03897 Final10/25/200610/26/200610/26/2006 10:09:18 AMAFAIL
Please inspect before 11:00 am. Work performed Ray Hall.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz corr. called 250.104(A)(1) nstill needs to bond hot and cold
ELE06-03952 Rough-In Permanent Service10/26/200610/26/200610/26/2006 9:37:31 AMAFAIL
Scheduled by a contractor via Hello! on 10/26/2006 at 7:11:38 AM. Contact: ###-####. corr, called 300.4(A)(1)&(D) nail plates and 11/4" parallel inside outside edges same for low voltage contr, 334.30 staple cables within 12" at panel, 314.20 outside light box garage exit door shall be flush with siding, needs protection cables garage attic access 6ft
ELE06-03952 Permanent Service10/26/200610/26/200610/26/2006 9:25:03 AMAPASS
Scheduled by a contractor via Hello! on 10/26/2006 at 7:11:38 AM. Contact: ###-####. r/i failed, p/s u/g new ok
ELE06-03939 Rough-In Permanent Service10/24/200610/26/200610/26/2006 9:12:08 AMAPASS
Glen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
r/i ok needs outlet back upstairs bed rm by closet called p/s u/g new ok
ELE06-03938 Rough-In Permanent Service10/24/200610/26/200610/26/2006 9:10:53 AMAPASS
Glen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
r/i ok needs outlet upstairs back upstairs bed rm by closet called, p/s u/g new ok
ELE06-02779 ELE-Aging Inspection10/26/200610/26/200610/26/2006 7:50:05 AM CANC
ELE06-03907 Final10/26/200610/26/200610/26/2006 7:45:47 AMAPASS
My cell number is ###-####, thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher