ELE06-02747
| ELE-Aging Inspection | 10/26/2006 | 10/26/2006 | 10/31/2006 10:29:01 AM | | DONE |
|
|
see final
|
ELE06-02746
| ELE-Aging Inspection | 10/26/2006 | 10/26/2006 | 10/31/2006 10:28:05 AM | | DONE |
|
|
see final
|
ELE06-01281
| Final | 10/26/2006 | 10/26/2006 | 10/26/2006 3:27:59 PM | P | DONE |
|
|
looked at signs, ok to final
|
ELE06-00081
| Final | 10/26/2006 | 10/26/2006 | 10/26/2006 3:26:54 PM | P | PASS |
|
|
looked at sign, ok to final
|
ELE06-03971
| Electrical Rough-In | 10/26/2006 | 10/26/2006 | 10/26/2006 3:26:12 PM | P | PART |
|
|
###-#### larry called, told elect about a couple 1 1/4" areas, marked on studs, kitchen, dining area, south side upper level only ok to cover, will call once wall changed for rest
|
ELE06-03413
| Final | 10/26/2006 | 10/26/2006 | 10/26/2006 3:23:09 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy met contr,left corr notice, nec 314.15(A) in wet locations, fittings shall be listed for use in wet locations, 110.26(A) work space about panel shall be 3' clear distance in front of panel, BCC kitchen area outlets shall operate, no violations shall be retained
|
ELE06-03701
| Permanent Service | 10/26/2006 | 10/26/2006 | 10/26/2006 3:19:57 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/26/2006 at 9:43:44 AM. Contact: ###-#### called, left corr notice, nec 110.26(A) work space height shall extend from grade to 6 1/2' above panel and shall be clear.
|
ELE06-03892
| Temporary Service | 10/26/2006 | 10/26/2006 | 10/26/2006 2:40:18 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/26/2006 at 7:56:36 AM. Contact: ###-####. corr made, t/s o/h n ok
|
ELE06-03959
| Electrical Rough-In | 10/25/2006 | 10/26/2006 | 10/26/2006 11:00:40 AM | A | PASS |
|
|
Uffer ground inspection. Any questions call Mike Carter.; Phone #: ###-#### Internet Inspection Request from: David Lamarque ok to pour gec
|
ELE06-03687
| Electrical Rough-In | 10/25/2006 | 10/26/2006 | 10/26/2006 10:30:32 AM | A | PASS |
|
|
READY FOR ROUGH-IN INSPECTION FOR REGER ADDITION. THANK YOU; Phone #: ###-#### Internet Inspection Request from: Barry Kendall ric ok
|
ELE06-03963
| Final | 10/25/2006 | 10/26/2006 | 10/26/2006 9:42:35 AM | A | PASS |
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-03967
| Permanent Service | 10/25/2006 | 10/26/2006 | 10/26/2006 9:22:10 AM | A | FAIL |
|
|
inspection for moving outside meter Internet Inspection Request from: Rowdy Monroe \alled left corr notice, nec 250.53(C)(2) shall install 2 grounding electrodes, 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be clear and concise, 230.24(A) service conductors shall be 8' above roof surface
|
ELE06-03960
| Electrical Rough-In | 10/26/2006 | 10/26/2006 | 10/26/2006 9:01:15 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, need to see u/g before p/s, see canc
|
ELE06-03960
| Rough-In Permanent Service | 10/25/2006 | 10/26/2006 | 10/26/2006 8:58:23 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see ri, need to see u/g before p/s , told contr to provide pot hole 2' deep to see if sweeps deep by house and garage
|