Inspections for the day of: Thursday, October 26, 2006.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00891 FIR-Aging Inspection10/26/200610/26/200610/31/2006 12:07:27 PM DEFR
FIR06-00797 INSP-Final Inspection10/26/200610/26/200610/27/2006 10:04:45 AMPDEFR
Inspection rescheduled.
BLD06-01379 FIRE-Final Inspection10/26/200610/26/200610/26/2006 3:46:32 PMPPASS
Life safety passed inspection. NOTE: No signature card available on site.
FIR06-00672 INSP-Sprinkler Rough-in10/26/200610/26/200610/26/2006 3:37:33 PMPPART
OH rough-in is okay to cover at the hard lid ceilings. Heads in the drop ceilings, UG supply and the riser are not completed.
BLD06-01193 FIRE-Final Inspection10/26/200610/26/200610/26/2006 2:56:15 PMPNR
The project related fire sprinkler permit must be finaled prior to life safety final.
FIR06-00431 INSP-Final Inspection10/25/200610/26/200610/26/2006 2:25:11 PMPPASS
Fire alarm work is satisfactory, inspection passed.
FIR06-00281 INSP-Final Inspection10/25/200610/26/200610/26/2006 1:47:15 PMPPART
Supply line flush completed satisfactory, contractor not ready for final at this time as the riser is not completed and missing some items such as calc. stickers, signs, locks for control valves, head box, etc., still need to perform alarm test.
FIR06-00820 INSP-Sprinkler Rough-in10/26/200610/26/200610/26/2006 1:05:47 PMPFAIL
Missing hanger on the arm-over to a closet head, one pendent is too close to a heat diffuser, need to replace a missing hanger on the NW main, head in the south lower soffit needs to be replaced due to paint and texture residue.
FIR06-00639 INSP-Sprinkler Rough-in10/25/200610/26/200610/26/2006 12:06:12 PMAPART
OH rough-in inspection for the 4th floor completed today. Noted elevator and garbage chute piping to heads at these locations is not yet complete, one W.D closet needs is missing a SW head, one pendent in a mec. closet is too close to the wall and blocked by ductwork, the provided as-built plans match the installation except as annotated.