ELE07-03615
| Rough-In Permanent Service | 10/24/2007 | 10/26/2007 | 10/26/2007 3:16:55 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Alan Lusk r/i p/s u/g new ok
|
ELE07-02990
| Final | 10/26/2007 | 10/26/2007 | 10/26/2007 3:16:31 PM | P | PASS |
|
|
tim Phone #: ###-#### ok
|
ELE07-02784
| Electrical Rough-In | 10/26/2007 | 10/26/2007 | 10/26/2007 1:59:38 PM | P | CANC |
|
|
chris Note: wall & ceiling Phone #: ###-#### this is the shell permit need new ele permit attached to tennant bld07-01151
|
ELE07-03630
| Electrical Rough-In | 10/26/2007 | 10/26/2007 | 10/26/2007 1:17:09 PM | P | PART |
|
|
Please do this inspection as late as possible. Not sure we need an electrical permit on this, but the general has pulled a building permit. We are adding outlets to a new wall from an existing circuit. Thanks Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa walls ok
|
ELE07-03620
| Electrical Rough-In | 10/25/2007 | 10/26/2007 | 10/26/2007 12:30:10 PM | P | PART |
|
|
underground and ground grid Phone #: ###-#### Internet Inspection Request from: Dan Wright u/g ok no E grid required
|
ELE07-02663
| ELE-Aging Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 10:57:47 AM | | DONE |
|
|
|
ELE07-02663
| Electrical Rough-In | 10/26/2007 | 10/26/2007 | 10/26/2007 10:57:35 AM | A | FAIL |
|
|
corr. called 350.6&356.6 shall not use jakes for lfnc, 300.3 no open wiring, 300.15 shall provide boxes for open splices, 600.5 &410.15(B) wires sshall exit pole as codes noted states
|
ELE07-03628
| Electrical Rough-In | 10/26/2007 | 10/26/2007 | 10/26/2007 10:18:38 AM | P | PASS |
|
|
added circuit to split up soffit lights. Please call Greg @ ###-#### and he will meet you there with a ladder. Thanks. Phone #: ###-#### Internet Inspection Request from: Carla Ward ok
|
ELE07-03628
| Final | 10/26/2007 | 10/26/2007 | 10/26/2007 10:18:22 AM | A | PASS |
|
|
added circuit to split up soffit lights. Please call Greg @ ###-#### and he will meet you there with a ladder. Thanks. Phone #: ###-#### Internet Inspection Request from: Carla Ward
|
ELE07-03627
| Rough-In Permanent Service | 10/25/2007 | 10/26/2007 | 10/26/2007 9:38:18 AM | A | PASS |
|
|
john Phone #: ###-#### r/i p/s u/g new ok
|
ELE07-03628
| Final | 10/25/2007 | 10/26/2007 | 10/26/2007 8:55:23 AM | A | CANC |
|
|
Please call Greg @ ###-#### and he will come with a ladder and meet you there. Greg will be in Boise Fri AM. Phone #: ###-#### Internet Inspection Request from: Carla Ward Inspection cancelled from web by: Carla Ward
|
ELE07-01431
| Permanent Service | 10/25/2007 | 10/26/2007 | 10/26/2007 8:33:31 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: kendall bender needs to bond water sized to 250.66T
|
ELE07-01429
| Permanent Service | 10/25/2007 | 10/26/2007 | 10/26/2007 8:32:47 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: kendall bender needs to bond water sized to 250.66T
|
ELE07-03629
| Permanent Service | 10/25/2007 | 10/26/2007 | 10/26/2007 8:03:24 AM | A | CANC |
|
|
SCOTT Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Tyler Bowen
|