FIR07-00694
| INSP-Conference | 10/19/2007 | 10/22/2007 | | A | |
|
|
PIV issue
|
FIR07-00140
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:39:26 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00148
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:39:01 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00151
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:38:35 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00143
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:38:10 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00146
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:37:45 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00141
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:37:16 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00142
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:36:52 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00145
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:36:26 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00149
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:36:01 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00150
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:35:36 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00039
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:35:03 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00023
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:34:36 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00028
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:34:06 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00027
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:33:36 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00038
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:33:10 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00026
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:32:45 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00035
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:32:05 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00031
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:31:36 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00040
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:31:11 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00037
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:30:41 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00030
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:30:01 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00024
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:27:51 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00025
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:23:37 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00036
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:22:46 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00022
| INSP-Sprinkler Rough-in | 10/25/2007 | 10/26/2007 | 10/29/2007 3:22:08 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00029
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:21:19 PM | P | PART |
|
|
Hydro test passed.
|
FIR07-00022
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:20:36 PM | P | PART |
|
|
Hydro test passed.
|
FIR06-00504
| INSP-Sprinkler Rough-in | 10/25/2007 | 10/26/2007 | 10/29/2007 3:19:39 PM | P | FAIL |
|
|
Duplicated inspection request already completed.
|
FIR06-00504
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 3:18:49 PM | P | FAIL |
|
|
Inspection for the OH rough-in at the common corridors on the 3rd thru 6th floors failed due to overspaced hangers at arm-overs, uprights need to be installed at mech/equip. rooms, incorrect head spacing at the 6th floor, noted sensing lines at the FP and JP are not correct per NFPA 20. The OH hydrostatic test passed.
|
FIR07-00857
| INSP-Final Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 5:14:21 PM | P | FAIL |
|
|
Missing coverage at one closet, hangers at two arm-overs are overspaced.
|
FIR07-00805
| INSP-Final Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 4:40:24 PM | P | PASS |
|
|
Test Kitchen system. relocate one nozzle due to coverage issue while on site.test complete. Per KR
|
FIR07-00670
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 4:35:57 PM | P | FAIL |
|
|
test fire alarm panel, found that batterys in for fire alarm panel were incorrect, plans show 2, 110 AH batterys the batterys on site were only 50 AH, need to put in corrected batterys. Halway by restrooms will need a smoke added due to change in the plans. Elevator does not recall, does'nt have recall capabilities, could not verify detector in elevator shaft no access. relocate detector in kitchen. per KR
|
BLD07-02051
| FIRE-Final Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 4:18:28 PM | P | FAIL |
|
|
Need approved plans on site for review, exit sign at the main entry/exit door did not function on battery backup, need to test EM lighting.
|
FIR07-00716
| INSP-Final Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 4:13:13 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00400
| FIR-Aging Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 1:23:07 PM | | DEFR |
|
|
work in progress
|
BLD07-00900
| FIRE-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 1:22:30 PM | A | FAIL |
|
|
Two exit stairways as indicated on the scope of work are not yet complete, provide one PFE for the 2nd floor hall/ mech. room area, repair exit signs and existing EM lights on the 1st floor, provide approved hardware at the RR doors, install exit signs for the first floor office area as discussed.
|
FIR07-00441
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 12:43:53 PM | A | PART |
|
|
Verified corrections have been completed, final pending resubmitted plans reflecting all field modifications.
|
FIR06-00007
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 12:41:11 PM | A | PART |
|
|
Tested remainder of the second floor devices, noted two SD installed too close to HVAC registers, door hardware at the inactive leaf at the west set of fire doors to the skybridge is not approved, corrections from the previous inspection are complete.
|
BLD07-01859
| FIRE-Final Inspection | 10/23/2007 | 10/26/2007 | 10/26/2007 12:32:54 PM | A | FAIL |
|
|
need to change door hardware on restroom and confrence room. need to istall exit light at main entrance. Per KR.
|
FIR07-00736
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 12:29:06 PM | A | PART |
|
|
Two areas not test due to no access,see notes on aprove set of city plans.as per KR
|