Inspections for the day of: Friday, October 26, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00769 INSP-Final Inspection10/25/200710/26/200710/30/2007 2:38:14 PMPPASS
Permit finaled. Tamper switch operates correctly.
FIR07-00726 INSP-Sprinkler Rough-in/Hydro10/26/200710/26/200710/26/2007 5:21:00 PMPFAIL
OH hydro test failed
FIR07-00336 INSP-Sprinkler Rough-in/Hydro10/25/200710/26/200710/26/2007 4:43:29 PMAFAIL
OH hydro test failed
BLD06-02604 FIRE-Final Inspection10/25/200710/26/200710/26/2007 4:16:07 PMAFAIL
The duct smoke detectors need to be tested and proven with a manometer tester or removed since they are not required by code. The exit sign out of the kitchen/exterior door needs repaired and the emergency light in the womens restroom needs repaired.
BLD06-03515 FIRE-Final Inspection10/24/200710/26/200710/26/2007 4:13:31 PMAFAIL
The smoke control system still has issues being worked out by the third party engineer Jerry Oneal. All other life safety items in the new medical wing are ok.
FIR07-00671 INSP-Final Inspection10/25/200710/26/200710/26/2007 4:11:35 PMAFAIL
See mike timmermans notes for items tested and deficiencies such as the smoke detectors too close to the supply registers and the smoke detectors spaced in the areas where beams are 20" deep.
FIR07-00380 INSP-Final Inspection10/25/200710/26/200710/26/2007 4:08:10 PMAFAIL
The strobes now shutdown with the horns but the smoke control system still has issues. One duct smoke detector was found to be mounted incorrectly and is in the process of being fixed.
FIR07-00766 INSP-Sprinkler Rough-in10/25/200710/26/200710/26/2007 1:26:47 PMAFAIL
The tenting is still inadequate in areas. I did not find the framer when I was on site but the builder called me later and I let him know the areas of concern. He will fix these and call it back in for monday.
BLD07-02247 FIRE-Final Inspection10/25/200710/26/200710/26/2007 1:21:29 PMAPASS
Life safety passed.
FIR07-00630 FIR-Aging Inspection10/26/200710/26/200710/26/2007 8:27:42 AM NR
work is in progress