FIR07-00769
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/30/2007 2:38:14 PM | P | PASS |
|
|
Permit finaled. Tamper switch operates correctly.
|
FIR07-00726
| INSP-Sprinkler Rough-in/Hydro | 10/26/2007 | 10/26/2007 | 10/26/2007 5:21:00 PM | P | FAIL |
|
|
OH hydro test failed
|
FIR07-00336
| INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/26/2007 4:43:29 PM | A | FAIL |
|
|
OH hydro test failed
|
BLD06-02604
| FIRE-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 4:16:07 PM | A | FAIL |
|
|
The duct smoke detectors need to be tested and proven with a manometer tester or removed since they are not required by code. The exit sign out of the kitchen/exterior door needs repaired and the emergency light in the womens restroom needs repaired.
|
BLD06-03515
| FIRE-Final Inspection | 10/24/2007 | 10/26/2007 | 10/26/2007 4:13:31 PM | A | FAIL |
|
|
The smoke control system still has issues being worked out by the third party engineer Jerry Oneal. All other life safety items in the new medical wing are ok.
|
FIR07-00671
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 4:11:35 PM | A | FAIL |
|
|
See mike timmermans notes for items tested and deficiencies such as the smoke detectors too close to the supply registers and the smoke detectors spaced in the areas where beams are 20" deep.
|
FIR07-00380
| INSP-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 4:08:10 PM | A | FAIL |
|
|
The strobes now shutdown with the horns but the smoke control system still has issues. One duct smoke detector was found to be mounted incorrectly and is in the process of being fixed.
|
FIR07-00766
| INSP-Sprinkler Rough-in | 10/25/2007 | 10/26/2007 | 10/26/2007 1:26:47 PM | A | FAIL |
|
|
The tenting is still inadequate in areas. I did not find the framer when I was on site but the builder called me later and I let him know the areas of concern. He will fix these and call it back in for monday.
|
BLD07-02247
| FIRE-Final Inspection | 10/25/2007 | 10/26/2007 | 10/26/2007 1:21:29 PM | A | PASS |
|
|
Life safety passed.
|
FIR07-00630
| FIR-Aging Inspection | 10/26/2007 | 10/26/2007 | 10/26/2007 8:27:42 AM | | NR |
|
|
work is in progress
|