Inspections for the day of: Wednesday, October 26, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00645 ELE-Aging Inspection10/26/201110/26/201110/28/2011 6:29:13 AM DONE
see final
ELE10-02225 ELE-Aging Inspection10/26/201110/26/201110/27/2011 6:24:50 AM DONE
still under construction
ELE11-02339 Final10/26/201110/26/201110/26/2011 3:22:35 PMPPASS
>> Inspection requested via web by Stephanie White ok final
ELE11-02113 Final10/26/201110/26/201110/26/2011 2:44:52 PMPPASS
Call Dene for the access code.
Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ok final
ELE11-02433 Final10/26/201110/26/201110/26/2011 2:12:24 PMPFAIL
To access hot tub go thru gate on left side of house. >> Inspection requested via web by Terry Scott called, shall label breakers, provide receptacle within 6 -20' of tub, NEC 110.22, & 680.22
ELE11-02131 Permanent Service10/26/201110/26/201110/26/2011 1:24:07 PMPFAIL
Cory Phone #: ###-#### mey owners, contractor shall provide minimum 10' clearance ground to drip loop, get rid of white ground wire
ELE11-02429 Permanent Service10/26/201110/26/201110/26/2011 12:33:56 PMPPASS
Phone #: ###-#### >> Inspection requested via web by mike brown p/s o/h rec ok
ELE11-02427 Conference10/26/201110/26/201110/26/2011 12:20:54 PMPDONE
Need conference on remodel, any questions call Jake @###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose talked about remodel and extent of upgrade to existing wiring
ELE11-02426 Electrical Rough-In10/25/201110/26/201110/26/2011 10:32:44 AMACANC
Phone #: ###-#### >> Inspection requested via web by Alan Lusk contractor wanted pm inspection
ELE11-02124 Final10/25/201110/26/201110/26/2011 10:30:42 AMAPASS
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI corrections made, ok final
ELE08-02423 Final10/25/201110/26/201110/26/2011 10:30:07 AMAPART
B2 L3 Units & hallway. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy corridor ceiling floor 1 only ok cover, corridors 2,3 ok final, rooms floors 2,3 ok part final