FIR14-00724 INSP-Final Inspection10/21/201510/26/201510/26/2015 2:59:13 PMAPART
Fire alarm system test of wings F & G, including all unit SDs. corridor SDs, manual pulls, notification devices (audibility), FSDs, elevator recall functions, etc. All tested OK. Two unit SDs had to be reprogrammed to activate correctly.
NOTE: All fire sprinkler system testing completed with wing E test.
FIR14-00725 INSP-Final Inspection10/21/201510/26/201510/26/2015 2:56:12 PMAPART
Fire alarm system test for parking garage #2, which is under wings EF&G.=, including manual pulls, elevator recall and shunt trip functions, and audio/visual notification devices - all tested OK