ELE16-03481
| Electrical Rough-In | 10/26/2016 | 10/26/2016 | 10/26/2016 3:30:21 PM | P | FAIL |
|
|
Wesley Phone #: ###-#### 210.52- Kitchen counter top area shall not be more than 24" from a receptacle area. Peninsula receptacle shall be located at end of counter with in 12" of counter top and not more than 6" under overhang. 310.15- Wiring required for 20 amp receptacle outlets shall be 12 guage, 14-2 installed.
|
ELE16-03481
| Conference | 10/26/2016 | 10/26/2016 | 10/26/2016 3:24:55 PM | P | DONE |
|
|
Wesley Phone #: ###-#### Discussed requirements for receptacles in east wall kitchen remodel. All receptacle outlets serving counter top areas shall be on 20 amp circuit, tamper resistant and GFCI protected. Peninsula receptacle shall be with in 12" vertical of counter top and not more than 6" under overhang also not point on counter top surface shall be more than 24" from receptacle.
|
ELE16-01946
| Electrical Rough-In | 10/26/2016 | 10/26/2016 | 10/26/2016 2:40:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Ceiling in basement, east gym wall, framed wall in west stair as noted on contractor print rough in ok cover.
|
ELE16-03157
| Permanent Service | 10/26/2016 | 10/26/2016 | 10/26/2016 1:53:05 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Needed rough in inspection
|
ELE16-03157
| Electrical Rough-In | 10/26/2016 | 10/26/2016 | 10/26/2016 1:52:43 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender Main gear provided overcurrent for TI panel. 480 Volt panel and transformers and associated panels rough in ok cover
|
ELE16-03460
| Rough-In Permanent Service | 10/26/2016 | 10/26/2016 | 10/26/2016 11:31:23 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s o/h n ok
|
ELE16-01838
| Electrical Rough-In | 10/25/2016 | 10/26/2016 | 10/26/2016 10:59:53 AM | A | PASS |
|
|
Gathering Bar Ground Level Stack 2 Wall R-I Phone #: ###-#### Inspection requested via web by Tom Betty Gathering bar millwork rough in ok cover
|
ELE16-02693
| Electrical Rough-In | 10/25/2016 | 10/26/2016 | 10/26/2016 10:35:04 AM | A | PASS |
|
|
Call Chris for inspection of stair 1 masonry. Phone #: ###-#### Inspection requested via web by Rafael Castillo Stack 6 stair 1 rough in ok cover
|
ELE16-02836
| Final | 10/25/2016 | 10/26/2016 | 10/26/2016 9:36:08 AM | A | FAIL |
|
|
access 1001 Phone #: ###-#### Inspection requested via web by David Nelson 110.12- Garage and weather proof receptacles not working.
|
ELE16-03468
| Temporary Service | 10/25/2016 | 10/26/2016 | 10/26/2016 9:00:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|