Inspections for the day of: Wednesday, October 26, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03481 Electrical Rough-In10/26/201610/26/201610/26/2016 3:30:21 PMPFAIL
Wesley Phone #: ###-####
210.52- Kitchen counter top area shall not be more than 24" from a receptacle area. Peninsula receptacle shall be located at end of counter with in 12" of counter top and not more than 6" under overhang.
310.15- Wiring required for 20 amp receptacle outlets shall be 12 guage, 14-2 installed.
ELE16-03481 Conference10/26/201610/26/201610/26/2016 3:24:55 PMPDONE
Wesley Phone #: ###-####
Discussed requirements for receptacles in east wall kitchen remodel. All receptacle outlets serving counter top areas shall be on 20 amp circuit, tamper resistant and GFCI protected. Peninsula receptacle shall be with in 12" vertical of counter top and not more than 6" under overhang also not point on counter top surface shall be more than 24" from receptacle.
ELE16-01946 Electrical Rough-In10/26/201610/26/201610/26/2016 2:40:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Ceiling in basement, east gym wall, framed wall in west stair as noted on contractor print rough in ok cover.
ELE16-03157 Permanent Service10/26/201610/26/201610/26/2016 1:53:05 PMPCANC
Phone #: ###-#### Inspection requested via web by kendall bender
Needed rough in inspection
ELE16-03157 Electrical Rough-In10/26/201610/26/201610/26/2016 1:52:43 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender
Main gear provided overcurrent for TI panel. 480 Volt panel and transformers and associated panels rough in ok cover
ELE16-03460 Rough-In Permanent Service10/26/201610/26/201610/26/2016 11:31:23 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
Rough in ok cover p/s o/h n ok
ELE16-01838 Electrical Rough-In10/25/201610/26/201610/26/2016 10:59:53 AMAPASS
Gathering Bar Ground Level Stack 2 Wall R-I Phone #: ###-#### Inspection requested via web by Tom Betty
Gathering bar millwork rough in ok cover
ELE16-02693 Electrical Rough-In10/25/201610/26/201610/26/2016 10:35:04 AMAPASS
Call Chris for inspection of stair 1 masonry. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Stack 6 stair 1 rough in ok cover
ELE16-02836 Final10/25/201610/26/201610/26/2016 9:36:08 AMAFAIL
access 1001 Phone #: ###-#### Inspection requested via web by David Nelson
110.12- Garage and weather proof receptacles not working.
ELE16-03468 Temporary Service10/25/201610/26/201610/26/2016 9:00:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok