Inspections for the day of: Wednesday, October 26, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00198 INSP-Alarm Testing10/26/201610/26/201610/26/2016 5:24:43 PMPDONE
Alarm testing complete for today. Items tested: Floor above floor below notification for all levels of the headquarters building levels parking through 9, automatic shutdown from in duct detection for air handler units 1,2 and 3, audio visual verification for headquarters stack 1 and 2 of level 1 and headquarters parking level, verified signals received from monitoring service, rooftop exhaust unit shutdown and heat trace monitoring for headquarters heat trace on fire sprinkler mains.
FIR16-00585 INSP-Sprinkler Rough-in10/26/201610/26/201610/26/2016 5:18:13 PMPPART
Hydrostatic test complete for new dry system installed at basement parking level. Rough in inspection complete for new dry system installed. 24 hour air test started at 2pm @ 40psi.
BLD16-02713 FIRE-Final Inspection10/25/201610/26/201610/26/2016 1:25:34 PMPCANC
Project not ready for final inspection, emergency egress lighting and exit signs are not installed, general contractor will reschedule life fire safety inspection to coincide with exit sign/egress lighting completion. This inspection request cancelled.
FIR16-00566 INSP-Final Inspection10/25/201610/26/201610/26/2016 1:23:47 PMPPASS
Final fire sprinkler inspection passed/complete.
BLD15-01500 FIRE-Final Inspection10/26/201610/26/201610/26/2016 12:14:26 PMPPASS
No fire sprinkler modifications, fire sprinkler riser has a current inspection tag, final fire alarm inspection passed/complete, knox box is in place, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR15-00895 INSP-Final Inspection10/25/201610/26/201610/26/2016 12:12:41 PMAPASS
Final fire alarm inspection passed/complete
BLD16-03840 FIRE-Final Inspection10/24/201610/26/201610/26/2016 11:24:52 AMAPART
Partial final for life fire safety complete. No fire sprinkler modifications, fire sprinkler risers have current inspection tags, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Tenant for this space has new racking installed, this BLD permit cannot be finalized until permit for racking (BLD16-02660) is issued/inspected and inspection for racking is passed.
FIR15-00782 INSP-Final Inspection10/25/201610/26/201610/26/2016 10:44:52 AMAPASS
Final fire alarm inspection passed/complete
FIR15-00787 INSP-Final Inspection10/25/201610/26/201610/26/2016 10:44:23 AMAPASS
Final fire alarm inspection passed/complete
FIR15-00749 INSP-Final Inspection10/25/201610/26/201610/26/2016 10:43:37 AMAPASS
Final fire sprinkler inspection passed/complete.
FIR15-00806 INSP-Final Inspection10/25/201610/26/201610/26/2016 10:42:49 AMAPASS
Final fire sprinkler inspection passed/complete.