BLD17-03237
| FIRE-Final Inspection | 10/26/2017 | 10/26/2017 | 10/27/2017 9:04:39 AM | P | FAIL |
|
|
Provide address and annual inspections for the fire extinguishers.
Samuel Phone #: ###-####
|
BLD16-04280
| FIRE-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 3:09:35 PM | P | FAIL |
|
|
I referred the contractor back to the plan reviewer due to questions on the review. Itmes include number of gates requiring panic hardware, door mags being used on the west side gate and possible exit signs or emergency lights in the pool area. Contractor did not have the small documents. Thumbturn dead bolts have been used on the Locker rooms where plans call for lever action. The canopy emergency lights did not work.
Please call ahead for access - Noah Phone #: ###-####
|
NAF17-00063
| INSP-Final | 10/26/2017 | 10/26/2017 | 10/26/2017 2:50:15 PM | P | FAIL |
|
|
Repair the exit sign/emergency light at the north exit and provide the correct height of address numbers.
|
FIR17-00114
| INSP-Final Inspection | 10/23/2017 | 10/26/2017 | 10/26/2017 2:06:00 PM | A | PASS |
|
|
Permit finaled. Supervisory signals were verified by Lee at all three buildings today.
|
FIR17-00147
| INSP-Final Inspection | 10/24/2017 | 10/26/2017 | 10/26/2017 2:05:41 PM | A | PASS |
|
|
Permit finaled. Supervisory signals were verified by Lee at all three buildings today.
|
FIR16-00284
| INSP-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 12:35:16 PM | A | FAIL |
|
|
Not ready for final yet but we did test the dry pipe system and the interconnection with the fire alarm panel. It appears that a rough-in inspection is still needed for the garage.
|
FIR16-00183
| INSP-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 12:33:37 PM | A | PASS |
|
|
Permit finaled
|
FIR16-00446
| INSP-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 12:32:47 PM | A | FAIL |
|
|
Not ready for final yet but we did test two of the three fire smoke dampers and the dry pipe system interconnects. Still waiting on plan modifications, elevator and fire doors.
|
FIR17-00305
| INSP-Sprinkler Rough-in | 10/25/2017 | 10/26/2017 | 10/26/2017 12:29:05 PM | A | PASS |
|
|
Overhead rough-in passed. Corrections have been made to the seismic bracing. No cover, except hardlids until the pendants/drops have been installed and verified.
|
FIR17-00303
| INSP-Sprinkler Rough-in | 10/25/2017 | 10/26/2017 | 10/26/2017 12:28:39 PM | A | PASS |
|
|
Overhead rough-in passed. Corrections have been made to the seismic bracing. No cover, except hardlids until the pendants/drops have been installed and verified.
|
BLD17-00073
| FIRE-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 10:42:23 AM | A | PASS |
|
|
Life safety passed.
Doug Phone #: ###-####
|
NAF17-00012
| INSP-Final | 10/25/2017 | 10/26/2017 | 10/26/2017 9:39:59 AM | A | DONE |
|
|
life safety passed
|
NAF17-00073
| INSP-Final | 10/25/2017 | 10/26/2017 | 10/26/2017 9:39:32 AM | A | DONE |
|
|
Permit finaled
|
FIR17-00540
| INSP-Final Inspection | 10/25/2017 | 10/26/2017 | 10/26/2017 8:54:22 AM | A | PASS |
|
|
Permit finaled
|
FIR17-00575
| INSP-Sprinkler Rough-in | 10/25/2017 | 10/26/2017 | 10/26/2017 7:32:06 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|