ELE18-04137
| Electrical Rough-In | 10/26/2018 | 10/26/2018 | 10/26/2018 4:43:10 PM | P | FAIL |
|
|
Underground - Scott Phone #: ###-#### 250.32- Equipment grounding conductor shall be installed where additional metallic connection exists to seperate building.
|
ELE18-04137
| Conference | 10/26/2018 | 10/26/2018 | 10/26/2018 4:34:16 PM | P | PASS |
|
|
Underground - Scott Phone #: ###-#### Discussed underground, type of receptacles in garage, 4 wire to seperate structure with metallic connections between, required bathroom circuits and receptacle locations, receptacle layout for kitchen and habitable room. Pamphlet given.
|
ELE18-02479
| Final | 10/26/2018 | 10/26/2018 | 10/26/2018 3:39:24 PM | P | FAIL |
|
|
Temporary Occupancy Inspection at the One Cap building level 10 ; 12. Contact Jon Novak Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 10 electrical contractor had not energized circuits for receptacles and furniture at time of inspection. 300.15- All wiring shall terminate in a box. Several sections of furniture still need connected to building wiring. 406.6- Receptacles shall be securely mounted to a box and covers in place. Tile being installed in break area, receptacles have been removed from boxes and hanging on wiring. 330.12- MC cable shall not be installed where subject to physical damage. Stubs to furniture along widow walls exposed on window frame and enter lower wall. Shall be installed in a protective conduit or channel. Unable to test this floor. Level 12 same as 10 unable to test. If contractor requests I offered to come in on Sunday to inspect. Informed contact must be made to building official and additional fee paid.
|
ELE18-01206
| Electrical Rough-In | 10/26/2018 | 10/26/2018 | 10/26/2018 1:52:14 PM | P | PART |
|
|
Please call Bobby for inspection of ceiling grid in area A of third floor and for R/I inspection of walls on 3rd floor area C. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo Checked electrical rooms on level 3. Informed panic hardware required prior to energizing. No walls in area C level 3 were inspected. Level 3 area A grid only rough in ok after temp wiring has been removed.
|
ELE18-02559
| Electrical Rough-In | 10/26/2018 | 10/26/2018 | 10/26/2018 1:48:58 PM | A | PASS |
|
|
Please call Gary for R/I inspection of walls in servery. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo No columns, or hardlids. Walls only servery rough in ok cover
|
ELE18-03949
| Rough-In Permanent Service | 10/25/2018 | 10/26/2018 | 10/26/2018 11:44:13 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover p/s u/g n ok
|
ELE18-04132
| Final | 10/25/2018 | 10/26/2018 | 10/26/2018 11:09:22 AM | A | PASS |
|
|
Call ahead // UFER insp // David Phone #: ###-#### Final ok
|
ELE18-04132
| Electrical Rough-In | 10/26/2018 | 10/26/2018 | 10/26/2018 11:08:59 AM | P | PASS |
|
|
Call ahead // UFER insp // David Phone #: ###-#### Permit for concrete encased electrode only. Adding concrete encased electrode after foundation pour complete. Installed on top of footing rough in ok cover
|
ELE18-03942
| Rough-In Permanent Service | 10/25/2018 | 10/26/2018 | 10/26/2018 10:52:36 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.7- Installations shall be complete. Empty light box in garage ceiling. 340.10(4)- UF shall comply with 334. 334.30 UF shall be secured with in 12" of entering PVC to island. 352.28- Cut ends of PVC shall have rough edges removed. 352.46- Where UF enter or emerges from PVC they shall be protected from damage by bushings.
|
ELE18-02542
| Final | 10/25/2018 | 10/26/2018 | 10/26/2018 9:58:49 AM | A | NH |
|
|
Corbin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg No answer at door. Owner stated living in basement on previous inspection. Due to residence occupied someone must be home fro entry.
|
ELE18-03762
| Final | 10/25/2018 | 10/26/2018 | 10/26/2018 9:25:47 AM | A | FAIL |
|
|
Contact Lance if space is locked up 208.703.2035 Phone #: ###-#### Inspection requested via web by David Feller 404.9- All swich covers shall be installed. 406.6- All receptacles covers shall be installed. 404.9
|