Inspections for the day of: Monday, October 27, 2003.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03264 Rough-In Permanent Service10/24/200310/27/200310/27/2003 12:00:00 AMAFAIL
Installed new circuit from panel to furnace equipment under house. Meet owner 1 block away @ 2812 N. 26th St. Contact Ted Hamlin ###-#### hm. ###-#### cell.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. posted called 110.3(B) use manufactures listed breakers, 210.63 needs outlet with gfci for equipment in crawl space, and 210.70(A)(3) light fixture and switch at point of entry to crawl space 10/27/2003 9:05:52 AM
ELE03-03345 Permanent Service10/24/200310/27/200310/27/2003 12:00:00 AMAFAIL
we need to have you look at the wire were puting in for ufer ground; Phone #: ###-#### Internet Inspection Request from: William Zerfas see added r/i for concrete encased electrode 10/27/2003 9:28:22 AM
ELE03-03182 Temporary Service10/24/200310/27/200310/27/2003 12:00:00 AMAFAIL
byron; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted called 110.3(B) milbank instructions states 2 pole breakers only 10/27/2003 8:37:58 AM
ELE03-03376 Temporary Service10/24/200310/27/200310/27/2003 12:00:00 AMAPASS
###-#### allen t/s u/g new ok 10/27/2003 10:16:14 AM
ELE03-03345 Electrical Rough-In10/27/200310/27/200310/27/2003 12:00:00 AMAFAIL
r/i for electrode failed needs 20 ft of # 4 copper in contact with earth called
ELE02-02929 Final10/27/200310/27/200310/27/2003 12:00:00 AMPPASS
call for access ###-####- warren ok 10/27/2003 1:58:50 PM
ELE03-03199 Electrical Rough-In10/27/200310/27/200310/27/2003 12:00:00 AMPPART
roger; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie outside new entry lights 10/27/2003 2:46:44 PM
ELE03-02906 Electrical Rough-In10/24/200310/27/200310/27/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 10/24/2003 at 4:55:07 PM. Contact: ###-####. 300.11 shall install wires from structure to grid to support cables, and renove caddy clips that support cables on grid 10/27/2003 3:46:38 PM
ELE03-02550 Final10/27/200310/27/200310/27/2003 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 10/27/2003 at 7:25:02 AM. Contact: ###-####. everything ok , except need televisions installed cords above ceiling, and xray unit on site so listing can be checked 10/27/2003 12:51:19 PM