MIS03-00204
| FIR-Final | 10/17/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | A | FAIL |
|
|
###-#### janice Provide annual inspection for the existing fire extinguisher, provide "door to remain unlocked...." sticker, and provide new exit sign at the rear exit. 10/27/2003 10:39:26 AM
|
FIR03-00202
| INSP-Final Inspection | 10/21/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | A | FAIL |
|
|
all devices tested ok but there is a problem with the ADT Focus dialer. To sent a signal to the central station it appears a person has to manually push the reset button each time a signal comes comes into the panel. Alarm signals are not getting to central station within the 90 seconds allowed by coded and may not even get there unless that button gets pushed. 10/27/2003 10:10:03 AM
|
FIR03-00507
| INSP-Final Inspection | 10/21/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | A | CANC |
|
|
This inspection was cancelled due to problems with central station communications. all devices tested ok but there is a problem with the ADT Focus dialer. To sent a signal to the central station it appears a person has to manually push the reset button each time a signal comes comes into the panel. Alarm signals are not getting to central station within the 90 seconds allowed by coded and may not even get there unless that button gets pushed. 10/27/2003 10:11:05 AM
|
FIR03-00501
| INSP-Final Inspection | 10/24/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | A | FAIL |
|
|
No items have been corrected from the first correction notice 10/27/2003 11:31:04 AM
|
BLD03-02028
| FIRE-Final Inspection | 10/27/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | A | CANC |
|
|
wrong inspection called in 10/27/2003 10:07:12 AM
|
BLD03-01954
| FIRE-Final Inspection | 10/27/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | A | PASS |
|
|
fire life safety finaled
|
BLD03-01380
| FIRE-Final Inspection | 10/27/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | P | FAIL |
|
|
paint curbing on the north and south side access roads to the portables
|
FIR03-00626
| INSP-Sprinkler Rough-in | 10/27/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | P | FAIL |
|
|
###-#### eric Inspection was for the two pendant heads installed in the entry way. The north head is ok but the south pendant has been hung from sprinkler eq bracing. All other hangers in the space need retaining straps and attachments to the top of structure 10/27/2003 4:31:53 PM
|
FIR03-00591
| INSP-Final Inspection | 10/24/2003 | 10/27/2003 | 10/27/2003 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/24/2003 at 5:16:44 PM. Contact: ###-####.
|