ELE05-03038
| Final | 10/27/2005 | 10/27/2005 | 10/27/2005 3:02:24 PM | P | NH |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called
|
ELE05-03918
| Temporary Service | 10/27/2005 | 10/27/2005 | 10/27/2005 2:20:25 PM | P | FAIL |
|
|
###-#### - jim called cor. use only sq. D breakers,240.21(A) 6ft 7" for any breaker space
|
ELE05-03186
| Permanent Service | 10/27/2005 | 10/27/2005 | 10/27/2005 1:32:41 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/27/2005 at 8:52:07 AM. Contact: ###-####. p/s u/g new ok
|
ELE05-00828
| Permanent Service | 10/27/2005 | 10/27/2005 | 10/27/2005 12:49:33 PM | P | FAIL |
|
|
faruk; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor met owner needs to grd to water pipe 250.52(A)(1)
|
ELE05-03858
| Rough-In Permanent Service | 10/21/2005 | 10/27/2005 | 10/27/2005 12:11:45 PM | P | FAIL |
|
|
steve-- ###-#### cor ,do not cover called let message, 250.64 (C)&(E) shall not splice GEC, and use conn. for GEC at panels,314.43 no nails or screws in plastic boxes,210.52(B) remove range hood from kit circuit, complete all makeup outside boxes
|
ELE05-03869
| Rough-In Permanent Service | 10/26/2005 | 10/27/2005 | 10/27/2005 10:55:10 AM | A | PASS |
|
|
daryl ###-#### ok p/s u/g new ok
|
ELE05-03901
| Electrical Rough-In | 10/26/2005 | 10/27/2005 | 10/27/2005 10:53:17 AM | A | PASS |
|
|
paul ###-#### ok
|
ELE05-03910
| Temporary Service | 10/26/2005 | 10/27/2005 | 10/27/2005 10:15:56 AM | A | FAIL |
|
|
rick ###-#### called drive grd rod flush needs conn. for GEC, ck for use for u/g
|
ELE05-03907
| Temporary Service | 10/26/2005 | 10/27/2005 | 10/27/2005 10:14:47 AM | A | FAIL |
|
|
rick ###-#### called, drive grd rod flush conn. for GEC, check for u/f, or use fpr u/g
|
ELE05-03908
| Temporary Service | 10/26/2005 | 10/27/2005 | 10/27/2005 10:13:12 AM | A | FAIL |
|
|
rick ###-#### called needs uf or use,for u/g and conn for GEC
|
ELE05-03909
| Final | 10/26/2005 | 10/27/2005 | 10/27/2005 9:32:52 AM | A | CANC |
|
|
Inspect lights and wiremold; Phone #: ###-#### Internet Inspection Request from: Dana Moyer notice posted called cannot do inspection till owner, secures all permits required for temp office trailer, talked wit Carol of COD and Tom of BLD
|
ELE05-03594
| Rough-In Permanent Service | 10/26/2005 | 10/27/2005 | 10/27/2005 8:30:47 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/26/2005 at 6:47:42 PM. Contact: ###-####. met with owner had conference, 300.4, 314.16, box fill,staple romex, complete all makeup
|
ELE05-02714
| ELE-Aging Inspection | 10/27/2005 | 10/27/2005 | 10/27/2005 7:39:25 AM | | NR |
|
|
wsuc
|
ELE05-02273
| Final | 10/26/2005 | 10/27/2005 | 10/26/2005 3:44:57 PM | A | PASS |
|
|
jim//please call prior; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok card signed
|