Inspections for the day of: Thursday, October 27, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02806 Permanent Service10/27/200510/27/200510/27/2005 5:08:39 PMPPART
Service Inspection; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked to contr, left corr notice, 110.3(B) 480V service shall be listed for service entrance, 376.23(A) and(B) wireway shall be as per 312.6, and 314.28(A)(2)
ELE05-03675 Electrical Rough-In10/27/200510/27/200510/27/2005 5:03:21 PMPPASS
cover on trench//dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to cover u/g
ELE05-03653 Rough-In Permanent Service10/26/200510/27/200510/27/2005 3:32:19 PMPPASS
Scheduled by a contractor via Hello! on 10/26/2005 at 10:21:53 AM. Contact: ###-####. ric ok , p/s u/g n ok
ELE05-03141 Final10/27/200510/27/200510/27/2005 2:15:15 PMPPASS
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL called contr to tighten one recpt, get lv wires off grid in clg, signed struct card, ok to final
ELE05-03914 Rough-In Permanent Service10/26/200510/27/200510/27/2005 1:26:56 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan ric ok, p/s u/g n ok
ELE05-03291 Final10/26/200510/27/200510/27/2005 10:02:45 AMAPASS
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis ok to final
ELE05-03859 Temporary Service10/26/200510/27/200510/27/2005 9:44:19 AMAPASS
###-#### Nicole t/s u/g n ok
ELE05-03902 Rough-In Permanent Service10/26/200510/27/200510/27/2005 9:30:48 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan corr made ric ok, p/s u/g n ok
ELE05-02806 Electrical Rough-In10/26/200510/27/200510/27/2005 8:59:15 AMAPASS
Phone #: ###-#### called cont, clg cover ok, add showroom recpts before final
ELE05-03674 Electrical Rough-In10/26/200510/27/200510/27/2005 8:30:20 AMAPASS
Need ceiling inspection to cover.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty front entry ceiling ok to cover
ELE04-04020 Final10/26/200510/27/200510/27/2005 8:07:42 AMAPART
Scheduled by a contractor via Hello! on 10/26/2005 at 1:52:39 PM. Contact: ###-####. see notes 10/26/05, signed t/o card noting notes.