ELE06-02796 ELE-Aging Inspection10/27/200610/27/200610/27/2006 4:13:18 PM NR
suc
ELE06-02320 Final10/27/200610/27/200610/27/2006 4:12:25 PMPPASS
changed bath fan light & changed bath ceiling light code on garage is 1031 enter Internet Inspection Request from: Melyne Davis corrections made, ok to final
ELE06-04001 Rough-In Permanent Service10/27/200610/27/200610/27/2006 4:11:29 PMPPASS
waiting for heater dogs to install fans in restrooms, been told they will be ready in time for pm inspect.; Phone #: ###-#### Internet Inspection Request from: dennis mcneely ric ok, p/s u/g n ok, told contr to verify and post address and to start core and shell elect work since this is ti permit
ELE06-03961 Electrical Rough-In10/25/200610/27/200610/27/2006 2:49:17 PMPPASS
jason; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok
ELE06-03693 Electrical Rough-In10/27/200610/27/200610/27/2006 2:48:20 PMPPASS
wayne ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok
ELE06-03797 Permanent Service10/27/200610/27/200610/27/2006 2:24:21 PMPPASS
paul ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s exst meter pak,2 meters, n ok
ELE06-03967 Permanent Service10/26/200610/27/200610/27/2006 1:18:54 PMPPASS
reinsepction, we cannot label the panel until the power is connected as we cannot check which breaker goes to what, ID Power will not hook up the power without the inspection first Internet Inspection Request from: Rowdy Monroe called, still need abrasion protection, and final, p/s o/h rec ok
ELE06-03662 Final10/27/200610/27/200610/27/2006 12:54:38 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney corr not made, fee due
ELE06-04003 Rough-In Permanent Service10/27/200610/27/200610/27/2006 12:28:56 PMPPASS
Lynn, these are for units 1536 thru 1542; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok, p/s u/g n ok
ELE06-03526 Final10/26/200610/27/200610/27/2006 11:45:57 AMAPASS
shannon - note: call 1/2 hr prior to going out ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left message to finish panel schedule, ok to final
ELE06-02392 Permanent Service10/26/200610/27/200610/27/2006 10:37:14 AMAPASS
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt p/s u/g n ok
ELE06-03966 Permanent Service10/26/200610/27/200610/27/2006 9:55:04 AMAFAIL
Bob Tomlinson ###-#### called contr, left corr notice, nec 110.26(A)(3) working space shall be clear from grade up to 6 1/2' over panel, IPCO requires min 2" mast for o/h service
ELE06-01275 Final10/27/200610/27/200610/27/2006 9:24:32 AMAPART
Reinpection for final. Contact Marvin Miller ###-####. Thank you; Phone #: ###-#### Internet Inspection Request from: Laura Longshaw met elect, left corr notice and added 2 week correction time for air comp and x-ray, signed t/o card
ELE06-03391 Final10/26/200610/27/200610/27/2006 9:22:29 AMAPASS
damon; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final, corr made
ELE06-03987 Temporary Service10/26/200610/27/200610/27/2006 8:47:59 AMAPASS
WE HAVE DISCONNECTED ALL OF THE EXISTING CIRCUITS EXCEPT THE DYER AND WOULD LIKE TEMPORARY SERVICE FOR TEMPORARY HEAT; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH t/s, exst meter pak, rec, ok
ELE06-03821 Final10/26/200610/27/200610/27/2006 8:29:19 AMAFAIL
Curtis; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called, left corr notice,BCC all installation shall be done, panel access shall be provided, left message
ELE06-03275 Electrical Rough-In10/26/200610/27/200610/27/2006 8:24:59 AMAPART
Scheduled by a contractor via Hello! on 10/26/2006 at 4:51:27 PM. Contact: ###-####. baths, mech room walls, lighting control wall, soffits ok to cover
ELE06-03987 Permanent Service10/26/200610/27/200610/26/2006 5:35:23 PMACANC
paul; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: BRIAN KEITH