Inspections for the day of: Friday, October 27, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00463 INSP-Sprinkler Rough-in/Hydro10/26/200610/27/200610/27/2006 4:20:56 PMPPASS
Overhead wet and dry systems including the fdc have passed the hydro tests.
FIR06-00573 INSP-Alarm Testing10/26/200610/27/200610/27/2006 4:20:17 PMAPASS
permit finaled
FIR06-00340 INSP-Supply line flush10/26/200610/27/200610/27/2006 2:54:15 PMAFAIL
Waited for 1/2 an hour but united water did not show up
MIS06-00281 FIR-Final10/26/200610/27/200610/27/2006 2:13:29 PMAFAIL
remove the manual flush bolts from the inactive leaf of the main exit, remove the thumbturn dead bolt from the rear exit, lower the fire extinguisher to 48", all of the sprinkler pendants are overspaced. This work will require a separate permit.
FIR06-00553 FIR-Aging Inspection10/27/200610/27/200610/27/2006 1:42:35 PM NR
Work is not yet complete
FIR06-00784 INSP-Final Inspection10/26/200610/27/200610/27/2006 12:34:18 PMAPASS
permit finaled
FIR05-00832 INSP-Final Inspection10/26/200610/27/200610/27/2006 9:45:48 AMAPASS
permit finaled
FIR06-00618 INSP-Supply line flush10/26/200610/27/200610/27/2006 8:47:46 AMAPASS
Underground flush passed.
FIR06-00616 INSP-Supply line flush10/26/200610/27/200610/27/2006 8:35:09 AMAPASS
Underground flush passed.
FIR06-00617 INSP-Supply line flush10/26/200610/27/200610/27/2006 8:34:50 AMAPASS
Underground flush passed.