PLM11-00907
| PLM-Aging Inspection | 10/27/2011 | 10/27/2011 | 10/28/2011 8:29:04 AM | | PASS |
|
|
|
PLM11-01149
| Plumbing Rough-in | 10/27/2011 | 10/27/2011 | 10/27/2011 5:01:40 PM | P | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Scott Hurren not ready
|
PLM11-01901
| Final | 10/26/2011 | 10/27/2011 | 10/27/2011 3:58:21 PM | A | PART |
|
|
>> Inspection requested via web by Josh Roper need to adjust mixing valve for 120 degree hot water need to have double check for lawn sprinkler tested and certified
|
PLM11-01106
| Final | 10/26/2011 | 10/27/2011 | 10/27/2011 3:55:33 PM | A | PART |
|
|
Phone #: ###-#### >> Inspection requested via web by Erin Whiting need to provide seperate water supply for chemical despencer above mop sink need to repipe trap for ice maker so trap seal is not less than two and not more than four inches need to install a vacuum breaker for washer-hose bedpan and shall be located not less than 5 feet above floor 2003 upc 603.4.19 talked to plumber on site need to recall when ready
|
PLM11-02190
| Plumbing Rough-in | 10/26/2011 | 10/27/2011 | 10/27/2011 11:31:34 AM | A | PASS |
|
|
Unit is open, just walk in. Phone #: ###-#### >> Inspection requested via web by Jason Gale rough-in ok
|
PLM11-02182
| Plumbing Rough-in | 10/26/2011 | 10/27/2011 | 10/27/2011 9:45:28 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by John Hensley
|
PLM11-02182
| DOC - Permit Finaled | 10/27/2011 | 10/27/2011 | 10/27/2011 9:45:19 AM | A | PASS |
|
|
|
PLM11-02180
| Water and/or Sewer | 10/26/2011 | 10/27/2011 | 10/27/2011 9:44:44 AM | A | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Dave Wood not ready contractor to recall when ready
|
PLM11-02179
| Water and/or Sewer | 10/26/2011 | 10/27/2011 | 10/27/2011 9:44:06 AM | A | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Dave Wood not ready
|