FIR11-00297
| INSP-Final Inspection | 10/27/2011 | 10/27/2011 | 10/27/2011 3:07:33 PM | P | FAIL |
|
|
The underground conduit connecting the three buildings appears to be PVC and not the metallic conduit as stated on the plans. After confiring with Doug Poedy it was clear in both NFPA 72 and NEC that the only options for the interbuilding fire alarm circuiting are: provide a metalic cable shield (grounded to the building electrode system), run in metalic conduit (grounded to the building electrode system), or provide isolation modules. As-builts will be needed reflecting what is used. Will also need the netcom verified. Mount the building maps. Devices are labeled building "b" and "c" but not building "a". Relabel devices for building "a" so that consistancy is maintained. All other items have been checked.
|
BLD11-02527
| FIRE-Final Inspection | 10/27/2011 | 10/27/2011 | 10/27/2011 11:58:48 AM | P | PASS |
|
|
life safety passed
|
BLD11-00406
| FIRE-Final Inspection | 10/27/2011 | 10/27/2011 | 10/27/2011 11:57:38 AM | P | PASS |
|
|
life safety passed
|
FIR11-00405
| INSP-Final Inspection | 10/26/2011 | 10/27/2011 | 10/27/2011 11:03:15 AM | A | FAIL |
|
|
The pizza oven suppression system can be finaled when the paper work is signed. Per the IMC commentary this type of oven can be installed under a type II hood so the duct/plenum nozzles are adequate. The other supression system, when activated, did not turn off the under hood lights. So it will need to be retested once the wiring has been corrected.
|
FIR11-00404
| INSP-Final Inspection | 10/26/2011 | 10/27/2011 | 10/27/2011 11:03:01 AM | A | FAIL |
|
|
The pizza oven suppression system can be finaled when the paper work is signed. Per the IMC commentary this type of oven can be installed under a type II hood so the duct/plenum nozzles are adequate. The other supression system, when activated, did not turn off the under hood lights. So it will need to be retested once the wiring has been corrected.
|
FIR11-00474
| INSP-Final Inspection | 10/27/2011 | 10/27/2011 | 10/27/2011 10:47:39 AM | A | PASS |
|
|
permit finaled
|
FIR11-00023
| INSP-Final Inspection | 10/27/2011 | 10/27/2011 | 10/27/2011 10:47:13 AM | A | PASS |
|
|
permit finaled
|
FIR11-00428
| INSP-Alarm Testing | 10/26/2011 | 10/27/2011 | 10/27/2011 10:46:23 AM | A | PASS |
|
|
permit finaled
|
BLD11-02527
| FIRE-Final Inspection | 10/26/2011 | 10/27/2011 | 10/27/2011 10:46:04 AM | A | FAIL |
|
|
Repair or remove the exit signs, provide single action hardware and remove the thumbturn lock on the rear exit door.
|
FIR11-00305
| INSP-Final Inspection | 10/26/2011 | 10/27/2011 | 10/27/2011 8:45:16 AM | A | PASS |
|
|
permit finaled
|