ELE14-02973
| Permanent Service | 10/27/2014 | 10/27/2014 | 10/27/2014 2:45:49 PM | P | CANC |
|
|
Final on Permanent Service needed Phone #: ###-#### Inspection requested via web by Randy Fletcher Wanted final
|
ELE14-02973
| Final | 10/27/2014 | 10/27/2014 | 10/27/2014 2:22:12 PM | P | FAIL |
|
|
Final on Permanent Service needed Phone #: ###-#### Inspection requested via web by Randy Fletcher 342.30(A)- Imc riser shall be secured with in 3' of enclosure. 250.64(B)- Grounding electrode conductor shall be secured in place. 408.4- Every circuit shall be identified as to its purpose
|
ELE12-00661
| ELE-Aging Inspection | 10/27/2014 | 10/27/2014 | 10/27/2014 1:36:33 PM | | DONE |
|
|
Waiting on owner
|
ELE14-01898
| Electrical Rough-In | 10/27/2014 | 10/27/2014 | 10/27/2014 1:24:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Underground to post lights and house rough in ok cover
|
ELE14-02513
| Final | 10/27/2014 | 10/27/2014 | 10/27/2014 12:39:37 PM | P | PASS |
|
|
Mike Phone #: ###-#### Final ok
|
ELE14-02467
| Final | 10/27/2014 | 10/27/2014 | 10/27/2014 12:38:59 PM | P | PASS |
|
|
Mike Phone #: ###-#### Final ok
|
ELE14-02896
| Electrical Rough-In | 10/24/2014 | 10/27/2014 | 10/27/2014 10:42:07 AM | A | PASS |
|
|
Wall inspection for cover call if you need access. Phone #: ###-#### Inspection requested via web by robert feller Wall rough in ok cover
|
ELE14-02905
| Final | 10/24/2014 | 10/27/2014 | 10/27/2014 10:05:24 AM | A | PASS |
|
|
Inspection requested via web by Kelly Felin AC final ok
|
ELE14-02905
| Electrical Rough-In | 10/27/2014 | 10/27/2014 | 10/27/2014 10:04:29 AM | P | PASS |
|
|
Inspection requested via web by Kelly Felin AC rough in ok
|
GCE14-00156
| GCE-Rough-In | 10/24/2014 | 10/27/2014 | 10/27/2014 9:44:18 AM | A | PASS |
|
|
Micheal ###-#### ceiling grid inspection requested; call for access code if needed Grid rough in ok cover
|
ELE14-02915
| Rough-In Permanent Service | 10/25/2014 | 10/27/2014 | 10/27/2014 9:24:42 AM | A | PASS |
|
|
new addition and service located around back. Phone #: ###-#### Inspection requested via web by shane vigil Rough in ok cover p/s o/h n ok
|