Inspections for the day of: Thursday, October 27, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02982 ELE-Aging Inspection10/27/201610/27/201611/2/2016 2:28:33 PM PASS
Still under construction
ELE16-03309 Final10/27/201610/27/201610/27/2016 3:19:32 PMPPASS
DA Davidson Suite 1800 conference room Phone #: ###-#### Inspection requested via web by steve ragan
Final ok
ELE16-00089 Electrical Rough-In10/27/201610/27/201610/27/2016 3:18:40 PMPFAIL
Call Pierce for kitchen ceiling inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo
300.11- Luminaires shall be supported independant of grid. Few fixtures missed and others with support wires at steep angles providing no support.
300.15- couple open boxes, 1 near hood still being worked on, 2nd above janitors closet door.
ELE16-01708 Final10/26/201610/27/201610/27/2016 1:26:30 PMPNH
Contact is Derek Ball. Please call 1 hour prior to arriving on site so cabinet can be unlocked Phone #: ###-#### Inspection requested via web by Scott Campbell
No return phone call from contact. Cabinet locked as noted shall recall
ELE16-02922 Electrical Rough-In10/26/201610/27/201610/27/2016 11:26:22 AMAPASS
We are requesting a wall and ceiling rough-in inspection for tomorrow 10/27/16 in the morning. Our onsite contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Shall provide removable covers in ceiling to access junction boxes above hardlid. Bar area wall and hardlid rough in ok cover
ELE16-02693 Electrical Rough-In10/26/201610/27/201610/27/2016 11:24:39 AMAPASS
Call Chris for inspection of stair 1 ; 2 masonry. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Stack 7 stair 1 and 2 rough in ok cover
ELE16-02836 Final10/26/201610/27/201610/27/2016 9:51:20 AMAFAIL
Access 1001 Phone #: ###-#### Inspection requested via web by David Nelson
110.3- Receptacle on back of house shows miswire. Shall be connected as per instructions.
210.8- All outdoor receptacle outlets shall have GFCI protection. receptacle on back of garage.
ELE16-03463 Temporary Service10/25/201610/27/201610/27/2016 9:29:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by danny perrine
250.52(A)(5)- Ground rod shall be 8' in length
ELE16-03464 Temporary Service10/25/201610/27/201610/27/2016 9:28:58 AMAFAIL
Phone #: ###-#### Inspection requested via web by danny perrine
250.52(A)(5)- Ground rod shall be 8' in length.
ELE16-03467 Rough-In Permanent Service10/25/201610/27/201610/27/2016 8:56:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
rough in ok cover p/s u/g n ok