ELE12-02982
| ELE-Aging Inspection | 10/27/2016 | 10/27/2016 | 11/2/2016 2:28:33 PM | | PASS |
|
|
Still under construction
|
ELE16-03309
| Final | 10/27/2016 | 10/27/2016 | 10/27/2016 3:19:32 PM | P | PASS |
|
|
DA Davidson Suite 1800 conference room Phone #: ###-#### Inspection requested via web by steve ragan Final ok
|
ELE16-00089
| Electrical Rough-In | 10/27/2016 | 10/27/2016 | 10/27/2016 3:18:40 PM | P | FAIL |
|
|
Call Pierce for kitchen ceiling inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo 300.11- Luminaires shall be supported independant of grid. Few fixtures missed and others with support wires at steep angles providing no support. 300.15- couple open boxes, 1 near hood still being worked on, 2nd above janitors closet door.
|
ELE16-01708
| Final | 10/26/2016 | 10/27/2016 | 10/27/2016 1:26:30 PM | P | NH |
|
|
Contact is Derek Ball. Please call 1 hour prior to arriving on site so cabinet can be unlocked Phone #: ###-#### Inspection requested via web by Scott Campbell No return phone call from contact. Cabinet locked as noted shall recall
|
ELE16-02922
| Electrical Rough-In | 10/26/2016 | 10/27/2016 | 10/27/2016 11:26:22 AM | A | PASS |
|
|
We are requesting a wall and ceiling rough-in inspection for tomorrow 10/27/16 in the morning. Our onsite contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Shall provide removable covers in ceiling to access junction boxes above hardlid. Bar area wall and hardlid rough in ok cover
|
ELE16-02693
| Electrical Rough-In | 10/26/2016 | 10/27/2016 | 10/27/2016 11:24:39 AM | A | PASS |
|
|
Call Chris for inspection of stair 1 ; 2 masonry. Phone #: ###-#### Inspection requested via web by Rafael Castillo Stack 7 stair 1 and 2 rough in ok cover
|
ELE16-02836
| Final | 10/26/2016 | 10/27/2016 | 10/27/2016 9:51:20 AM | A | FAIL |
|
|
Access 1001 Phone #: ###-#### Inspection requested via web by David Nelson 110.3- Receptacle on back of house shows miswire. Shall be connected as per instructions. 210.8- All outdoor receptacle outlets shall have GFCI protection. receptacle on back of garage.
|
ELE16-03463
| Temporary Service | 10/25/2016 | 10/27/2016 | 10/27/2016 9:29:35 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 250.52(A)(5)- Ground rod shall be 8' in length
|
ELE16-03464
| Temporary Service | 10/25/2016 | 10/27/2016 | 10/27/2016 9:28:58 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 250.52(A)(5)- Ground rod shall be 8' in length.
|
ELE16-03467
| Rough-In Permanent Service | 10/25/2016 | 10/27/2016 | 10/27/2016 8:56:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok cover p/s u/g n ok
|