FIR16-00439
| INSP-Sprinkler Rough-in/Hydro | 10/26/2016 | 10/27/2016 | 10/28/2016 11:52:33 AM | P | PASS |
|
|
Overhead hydro test passed
|
FIR16-00673
| INSP-Sprinkler Rough-in/Hydro | 10/27/2016 | 10/27/2016 | 10/27/2016 2:36:36 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
BLD16-01453
| FIRE-Final Inspection | 10/27/2016 | 10/27/2016 | 10/27/2016 2:25:30 PM | P | FAIL |
|
|
No city approved plans on site. I noted that the exit sign, emergency light and fire extinguishers are provided and tested ok.
|
FIR16-00502
| INSP-Final Inspection | 10/27/2016 | 10/27/2016 | 10/27/2016 2:04:24 PM | P | PASS |
|
|
Permit finaled. Forward flush passed
|
FIR16-00629
| INSP-Final Inspection | 10/26/2016 | 10/27/2016 | 10/27/2016 2:03:31 PM | P | PASS |
|
|
Permit finaled
|
FIR15-00683
| INSP-Final Inspection | 10/26/2016 | 10/27/2016 | 10/27/2016 1:13:38 PM | A | FAIL |
|
|
Need sticker on the outside alarm bell and overhead and underground test papers.
|
FIR15-00699
| INSP-Final Inspection | 10/26/2016 | 10/27/2016 | 10/27/2016 12:07:17 PM | P | FAIL |
|
|
Monitoring was not set up correctly and elevators where not ready to be tested. Will need to perform the entire test over. As-builts need to be submitted
|
NAF16-00057
| INSP-Sprinkler Rough-in/Hydro | 10/26/2016 | 10/27/2016 | 10/27/2016 10:23:41 AM | A | FAIL |
|
|
Stopped rough-in inspection on the dry system due to pipe routing changes including in the remote area. Stopped the rough-in inspection on the wet system due to pipe routing changes in the main that effects the remote area. I also noted a branchline size the did not match plan. Plans need to be re-submitted showing all pipe routing changes. Fitter is using 1/2 lag bolts in the bottom of the 2x6 structure. I need to verify that is ok.
|
FIR15-00522
| INSP-Final Inspection | 10/26/2016 | 10/27/2016 | 10/27/2016 9:49:21 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00657
| INSP-Final Inspection | 10/26/2016 | 10/27/2016 | 10/27/2016 9:48:37 AM | A | PASS |
|
|
Permit finaled
|
FIR16-00439
| INSP-Sprinkler Rough-in/Hydro | 10/26/2016 | 10/27/2016 | 10/26/2016 2:40:35 PM | A | CANC |
|
|
Gordon Rogers is contact. He will be on site. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes
|