Inspections for the day of: Thursday, October 27, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00439 INSP-Sprinkler Rough-in/Hydro10/26/201610/27/201610/28/2016 11:52:33 AMPPASS
Overhead hydro test passed
FIR16-00673 INSP-Sprinkler Rough-in/Hydro10/27/201610/27/201610/27/2016 2:36:36 PMPPASS
Rough-in passed. Piping can be covered.
BLD16-01453 FIRE-Final Inspection10/27/201610/27/201610/27/2016 2:25:30 PMPFAIL
No city approved plans on site. I noted that the exit sign, emergency light and fire extinguishers are provided and tested ok.
FIR16-00502 INSP-Final Inspection10/27/201610/27/201610/27/2016 2:04:24 PMPPASS
Permit finaled. Forward flush passed
FIR16-00629 INSP-Final Inspection10/26/201610/27/201610/27/2016 2:03:31 PMPPASS
Permit finaled
FIR15-00683 INSP-Final Inspection10/26/201610/27/201610/27/2016 1:13:38 PMAFAIL
Need sticker on the outside alarm bell and overhead and underground test papers.
FIR15-00699 INSP-Final Inspection10/26/201610/27/201610/27/2016 12:07:17 PMPFAIL
Monitoring was not set up correctly and elevators where not ready to be tested. Will need to perform the entire test over. As-builts need to be submitted
NAF16-00057 INSP-Sprinkler Rough-in/Hydro10/26/201610/27/201610/27/2016 10:23:41 AMAFAIL
Stopped rough-in inspection on the dry system due to pipe routing changes including in the remote area. Stopped the rough-in inspection on the wet system due to pipe routing changes in the main that effects the remote area. I also noted a branchline size the did not match plan. Plans need to be re-submitted showing all pipe routing changes. Fitter is using 1/2 lag bolts in the bottom of the 2x6 structure. I need to verify that is ok.
FIR15-00522 INSP-Final Inspection10/26/201610/27/201610/27/2016 9:49:21 AMAPASS
Permit finaled
FIR16-00657 INSP-Final Inspection10/26/201610/27/201610/27/2016 9:48:37 AMAPASS
Permit finaled
FIR16-00439 INSP-Sprinkler Rough-in/Hydro10/26/201610/27/201610/26/2016 2:40:35 PMACANC
Gordon Rogers is contact. He will be on site. Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes