Inspections for the day of: Friday, October 27, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03643 Electrical Rough-In10/27/201710/27/201710/27/2017 3:04:59 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley
Detached garage rough in ok cover
ELE17-00739 Final10/27/201710/27/201710/27/2017 2:42:06 PMPPASS
Please contact Sid with any questions or concerns ###-####

Thank you and have a nice weekend! Phone #: ###-#### Inspection requested via web by JENNY EMEL Final ok
ELE17-03473 Electrical Rough-In10/25/201710/27/201710/27/2017 1:30:03 PMPPART
Please call Tom with any questions. Phone #: ###-#### Inspection requested via web by Kevin Perez
Must allow time to move home runs to basement for new panel location.
Main floor only rough in ok cover
ELE14-00774 Final10/26/201710/27/201710/27/2017 12:20:29 PMANR
Please call Alisha prior to gain access, her
no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
Called contact for access and she stated job is not ready and would reschedule.
ELE17-02009 Final10/26/201710/27/201710/27/2017 12:13:04 PMAFAIL
Ron Phone #: ###-####
200.7(C)(1)- White conductor used for other than grounded conductor shall be re-identified. AC ungrounded conductor.
210.8- All GFCI devices shall be installed in a readily accessible location. Garage door GFI.
210.8(A)(5)- Receptacles outlets installed in unfinished areas shall have GFCI protection. Garage loft.
210.11(C)(3)- All receptacle outets installed in bathroom locations shall be on a 20 amp circuit. Powder bath 12ga installed on a 15 amp breaker.
210.63- A receptacle outlet shall be installed with in 25' of outdoor HVAC equipment.
210.70(A)(2)- Required lighting outlet located at garage lower man door not working. (Bulbs)
334.15(B)- Horizontal runs of NM cable in garage loft shall be protected from physical damage due to area unfinished.
422.31- A disconnecting means shall be provided for permenantly installed hood. 110.25 lockout acceptable.
ELE17-02778 Final10/27/201710/27/201710/27/2017 10:06:35 AMAPASS
4224 code Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE17-02653 Final10/27/201710/27/201710/27/2017 10:00:26 AMAPASS
4224 code Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE17-02779 Final10/27/201710/27/201710/27/2017 9:59:59 AMAPASS
4224 code Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE17-03623 Temporary Service10/26/201710/27/201710/27/2017 9:18:26 AMAPASS
Phone #: ###-#### Inspection requested via web by caleb Larson
t/s u/g n ok