Inspections for the day of: Friday, October 27, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-04833 Pressure Test10/27/201710/27/201710/27/2017 3:51:31 PMPPASS
Phone #: ###-#### Inspection requested via web by Joseph Profitt - 20lb gas
MEC17-04833 Rough-in10/27/201710/27/201710/27/2017 3:51:12 PMPFAIL
Phone #: ###-#### Inspection requested via web by Joseph Profitt - Need insulation shield on B-vent, missing exhaust fan in basement bathroom, Dryer vent?
MEC17-04753 Final10/27/201710/27/201710/27/2017 3:17:27 PMPPASS
MEC17-04616 Final10/24/201710/27/201710/27/2017 2:54:45 PMPPASS
Please call Amanda Muri at ###-#### about 30-60 minutes prior to inspection Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC17-02313 Final10/26/201710/27/201710/27/2017 2:29:27 PMPPASS
Water Heater tied in call Brandon for access. Phone #: ###-#### Inspection requested via web by David Tully
MEC17-04753 Final10/27/201710/27/201710/27/2017 1:26:34 PMPFAIL
Hello! This was NR yesterday. Please contact Robert @ ###-#### to confirm job is ready for inspection.

Thanks! Phone #: ###-#### Inspection requested via web by Rick Borg - Flue is back graded in the crawl space
MEC17-04826 Final10/27/201710/27/201710/27/2017 10:55:52 AMAPASS
Inspection requested via web by jeff jedlick
MEC17-04803 Pressure Test10/26/201710/27/201710/27/2017 10:13:07 AMAFAIL
The contractor would like to cover the trench that the new gas line is in. it is at 18" depth, and is currently under a pressure test. Thanks! Phone #: ###-#### Inspection requested via web by Jason Adams - Need to pressure test 20lbs on a 30lb gauge, need 18 gauge yellow tracer wire ran with gas piping