Inspections for the day of: Friday, October 27, 2017.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00544 INSP-Final Inspection10/26/201710/27/201710/27/2017 5:03:39 PMPFAIL
Pendant heads are blocked by surface mount light fixtures.
FIR17-00566 INSP-Final Inspection10/26/201710/27/201710/27/2017 5:03:04 PMPPASS
Permit finaled
BLD16-01058 FIRE-Conference10/26/201710/27/201710/27/2017 5:02:43 PMPDONE
Tenting of sprinkler lines in units 509-519 passed. Numerous corrections made while I was on site. I also made an entry in the project related fire sprinkler permit activites.
FIR16-00586 INSP-Sprinkler Rough-in10/27/201710/27/201710/27/2017 5:01:52 PMPPASS
Tenting of sprinkler lines in units 509-519 passed. Numerous corrections made while I was on site.
BLD16-02415 FIRE-Final Inspection10/27/201710/27/201710/27/2017 5:00:47 PMPCANC
Need to cancel due to time constraints. Hunter is going to reschedule for monday.

Contact: Hunter Gomez Phone #: ###-#### Inspection requested via web by Mike McHargue
BLD15-03489 FIRE-Final Inspection10/27/201710/27/201710/27/2017 5:00:07 PMPCANC
Need to cancel due to time constraints. Scott is going to reschedule for monday.

Scott Phone #: ###-#### Requesting TCO for balance of project (10th floor and 02 rooms).
BLD06-02324 FIRE-Final Inspection10/26/201710/27/201710/27/2017 3:12:33 PMAFAIL
Not ready for a final yet. Today we verified exit signs and emergency lights (two on first and one on third did not work), fire extinguishers appear ok, address appears ok, door hardware except for the access control (not tested yet) appears ok, need fire doors installed and tested at the elevator as well as fire alarm and fire sprinkler finals.
BLD17-00162 FIRE-Final Inspection10/26/201710/27/201710/27/2017 3:03:46 PMAFAIL
No inspection performed due to no small documents on site. I noted the need for a fire extinguisher and specific requirements for the storage of hazardous chemicals.
FIR16-00446 INSP-Final Inspection10/25/201710/27/201710/27/2017 3:01:07 PMACANC
Bob Thorton will be the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker
FIR17-00617 INSP-Sprinkler Rough-in10/26/201710/27/201710/27/2017 2:26:36 PMAPASS
Cover inspection at South Bore is passed and can be covered. This is from the Suez point of connection to Big Mike the locomotive.
FIR17-00473 INSP-Sprinkler Rough-in10/26/201710/27/201710/27/2017 2:24:43 PMAPASS
See the city approved plans for locations marked with todays date where sprinkler piping is ok for cover.
FIR17-00552 INSP-Final Inspection10/27/201710/27/201710/27/2017 1:43:14 PMPPASS
Jim Danes Phone #: ###-#### Inspection requested via web by Connie Danes
BLD17-01694 FIRE-Final Inspection10/25/201710/27/201710/27/2017 1:42:29 PMPFAIL
No city approved plans or small documents on site. No address is present. Knox box has been removed. Racking permit is not signed off yet, Contractor stated delayed egress locks are being utilized so I went over IFC requirements for delayed egress locks which includes connection with the existing fire alarm system. I also noted that the mechanical plans indicate seven duct smoke detectors to be installed. We called the mechanical installer and he stated that by using the exception in the IMC only one is required. He is going to get approval from the mechanical engineer to delete the non-required and provide to me. But the one required duct smoke detector again will need to be tied into the existing fire alarm system. I noted thumbturn dead bolts at the main exit. This was only a partial courtesy inspection since no approved documents are on site.

Smith Phone #: ###-####
FIR17-00537 INSP-Sprinkler Rough-in10/26/201710/27/201710/27/2017 11:07:13 AMAPASS
Rough-in passed. Piping can be covered.

Michael Phone #: ###-####
BLD17-02385 FIRE-Final Inspection10/26/201710/27/201710/27/2017 9:25:05 AMAPASS
Life safety passed.

Ed Phone #: ###-####
FIR17-00569 INSP-Final Inspection10/26/201710/27/201710/27/2017 8:54:19 AMAFAIL
Not ready for final due to the PIV not reporting correctly and I noted alot of the notofication devices are overspaced and the area behind the front counter has no coverage. No actual testing performed. I went over items with the tech. Plans are too small to read and do not show the communication means being used. As-builts or possibly plan modifications are needed.

Jeremy Berg Phone #: ###-####
FIR17-00205 INSP-Final Inspection10/26/201710/27/201710/27/2017 8:41:44 AMACANC
Not ready for final due to the project related fire alarm not being ready.
NAF17-00063 INSP-Final10/26/201710/27/201710/27/2017 8:40:57 AMADONE
Life safety passed