FIR03-00411
| FIR-Aging Inspection | 10/28/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | | NR |
|
|
Called Desbest and left message with Jim Danes about progress 10/29/2003 12:24:53 PM
|
FIR03-00491
| INSP-Final Inspection | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:24:21 PM. plans don't match installation - need resubmittals; area in southwest corner not protected with sprinklers; area under stairs not protected; need sign on drain 10/28/2003 8:26:59 AM
|
FIR03-00093
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:25:30 PM. r/i for 1-2-3 floors; TI work in progress on 3rd 10/28/2003 11:00:57 AM
|
FIR03-00139
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:36:58 PM. Contact: ###-####. hydro on standpipe okay 10/28/2003 12:59:26 PM
|
FIR03-00136
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:38:15 PM. Contact: ###-####.Scheduled by a contractor via Hello! on 10/27/2003 at 1:36:58 PM. Contact: ###-####. hydro on standpipe okay 10/28/2003 12:59:38 PM
|
FIR03-00135
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:39:19 PM. Contact: ###-####. hydro on standpipe okay 10/28/2003 12:59:54 PM
|
FIR03-00115
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:40:44 PM. Contact: ###-####. hydro on standpipe okay 10/28/2003 1:00:09 PM
|
FIR03-00138
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:41:39 PM. Contact: ###-####.S hydro on standpipe okay 10/28/2003 1:00:21 PM
|
FIR03-00137
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/27/2003 at 1:42:50 PM. Contact: ###-####. hydro on standpipe okay 10/28/2003 1:00:35 PM
|
FIR03-00008
| INSP-Sprinkler Rough-in/Hydro | 10/27/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | P | PART |
|
|
24 hour air test okay 10/28/2003 1:24:14 PM
|
BLD03-02047
| FIRE-Final Inspection | 10/28/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | P | PASS |
|
|
###-#### rob no fire sprinkler work or fire alarm work was needed; sprinkler monitoring only 10/28/2003 3:23:22 PM
|
FIR03-00538
| INSP-Sprinkler Rough-in | 10/28/2003 | 10/28/2003 | 10/28/2003 12:00:00 AM | P | PART |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover hard lid areas in first floor restroom; need architect verification for hanging off bottom cord of truss; need data submittal for verfication of unistrut size for 3 inch main on bottom cord - provide for field use 10/28/2003 4:07:36 PM
|