Inspections for the day of: Friday, October 28, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02522 Final10/28/200510/28/200510/28/2005 5:36:51 PMPPASS
###-#### - jay called contr, left survey, 110.3(B) garage gfci shall operate correctly,408.4 circuit directory shall id bedrooms
ELE05-03472 Permanent Service10/28/200510/28/200510/28/2005 3:39:54 PMPFAIL
###-#### - brian 480 volt service so property line 110.26 work space shall be provided about elect equip., BCC shall be able to inspect ground rods and gec
ELE05-03904 Electrical Rough-In10/28/200510/28/200510/28/2005 3:31:38 PMPPASS
###-#### corr made, ric ok, p/s u/g n ok
ELE05-03802 Final10/27/200510/28/200510/28/2005 12:23:04 PMPFAIL
Charlie Internet Inspection Request from: Melyne Davis called left message, left corr notice, 348.30 fmc shall be strapped, 408.4 circuit directory shall be explicit,BCC ceiling shall be left open, no violations shall be retained
ELE05-03910 Temporary Service10/27/200510/28/200510/28/2005 10:19:22 AMAFAIL
Scheduled by a contractor via Hello! on 10/27/2005 at 11:46:43 AM. Contact: ###-####. called conr, 250.24 gec shall be connected to gnded conductor
ELE05-03908 Temporary Service10/27/200510/28/200510/28/2005 10:12:50 AMAPASS
Scheduled by a contractor via Hello! on 10/27/2005 at 11:45:24 AM. Contact: ###-####. t/s u/g n ok
ELE05-03907 Temporary Service10/27/200510/28/200510/28/2005 10:06:18 AMAPASS
Scheduled by a contractor via Hello! on 10/27/2005 at 11:44:11 AM. Contact: ###-####. t/s u/g n ok
ELE05-03924 Electrical Rough-In10/27/200510/28/200510/28/2005 9:42:12 AMAFAIL
BONDING INSPECTION FOR EXISTING SWIMMING POOL. THANK YOU; Phone #: ###-#### Internet Inspection Request from: Barry Kendall called contr, BCC u/g shall be inspected before cover, 680.26(C) equipotential plane shall be raised 2" for concrete and inspected
ELE05-03241 Final10/28/200510/28/200510/28/2005 9:12:57 AMAPASS
per bob looked at 10/27/05, signed occ card, ok to final
ELE05-03781 Temporary Service10/28/200510/28/200510/28/2005 8:56:46 AMACANC
Scheduled by a contractor via Hello! on 10/28/2005 at 6:57:12 AM. Contact: ###-####. see ri
ELE04-04022 Final10/27/200510/28/200510/28/2005 8:23:00 AMANR
Scheduled by a contractor via Hello! on 10/27/2005 at 4:06:45 PM. Contact: ###-####. told contr to call when done
ELE05-03781 Electrical Rough-In10/28/200510/28/200510/28/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 10/28/2005 at 6:57:12 AM. Contact: ###-####. ok to cover u/g for gec