FIR05-00366
| INSP-Final Inspection | 10/28/2005 | 10/28/2005 | 10/28/2005 5:12:03 PM | P | CANC |
|
|
No time available for this inspection due to BODO project inspections.
|
FIR05-00564
| INSP-Sprinkler Rough-in | 10/27/2005 | 10/28/2005 | 10/28/2005 5:09:27 PM | A | PART |
|
|
Temporary approval given pending resubmittals for changed EOL location, office 102 may need notification depending on occupant load of more than two people.
|
BLD05-00626
| FIRE-Final Inspection | 10/27/2005 | 10/28/2005 | 10/28/2005 5:06:31 PM | A | PART |
|
|
Temporary occupancy approval granted with Dave Hanneman's permission pending duct detector testing and approval.
|
MIS05-00079
| FIR-Final | 10/27/2005 | 10/28/2005 | 10/28/2005 5:04:24 PM | A | PASS |
|
|
Life safety passed inspection, the items on correction notice have been amended.
|
FIR05-00075
| INSP-Alarm Testing | 10/27/2005 | 10/28/2005 | 10/28/2005 5:03:12 PM | A | PART |
|
|
A temporary approval was signed with Sam Rogers permission pending resubmittals for changed EOL, west elevator completion, permanent signage at the FACP room door.
|
FIR05-00520
| INSP-Final Inspection | 10/27/2005 | 10/28/2005 | 10/28/2005 5:00:15 PM | A | PART |
|
|
Fire sprinkler is acceptable when shell system is operational and approved.
|
FIR05-00531
| INSP-Sprinkler Rough-in | 10/27/2005 | 10/28/2005 | 10/28/2005 4:59:07 PM | A | FAIL |
|
|
AHU #1 and #2 do not match approved plan with respect to location and addressing, AV at back wall adjacent to registers is obstructed by clothing racks, AHU #3 detector needs to be relocated as discussed, provide resubmittals reflecting the required changes.
|
FIR05-00076
| INSP-Sprinkler Rough-in | 10/27/2005 | 10/28/2005 | 10/28/2005 4:55:36 PM | A | PART |
|
|
North elevator is still non-functional, provide resubmittals for all required changes.
|
FIR05-00372
| INSP-Sprinkler Rough-in | 10/27/2005 | 10/28/2005 | 10/28/2005 4:53:41 PM | A | FAIL |
|
|
See correction notices for listing of defficient items.
|
FIR05-00623
| INSP-Sprinkler Rough-in | 10/27/2005 | 10/28/2005 | 10/28/2005 4:51:37 PM | A | FAIL |
|
|
Duct smoke detector at unit #2 is in a poor location, relocate to an approved site as discussed.
|
FIR05-00326
| INSP-Sprinkler Rough-in/Hydro | 10/26/2005 | 10/28/2005 | 10/28/2005 12:23:16 PM | A | CANC |
|
|
No time available for this inspection today due to BODO projects.
|
MIS05-00186
| FIR-Final | 10/27/2005 | 10/28/2005 | 10/28/2005 12:18:59 PM | A | FAIL |
|
|
brenda; Phone #: ###-#### Per Brenda the building address numbers have not yet been posted, still need to verify fire extinguishers and hardware issues.
|
MIS05-00186
| FIR-Final | 10/27/2005 | 10/28/2005 | 10/28/2005 12:16:56 PM | A | CANC |
|
|
Duplicate inspection already called in.
|
FIR05-00576
| INSP-Conference | 10/27/2005 | 10/28/2005 | 10/28/2005 9:42:34 AM | P | CANC |
|
|
this is Grants; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
FIR05-00075
| INSP-Sprinkler Rough-in | 10/27/2005 | 10/28/2005 | 10/28/2005 12:00:00 AM | A | CANC |
|
|
brian ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
FIR05-00089
| INSP-Final Inspection | 10/28/2005 | 10/28/2005 | 10/28/2005 12:00:00 AM | P | PART |
|
|
Temporary approval given with Dave Hanneman"s permission pending flow test at roof standpipe, 2nd floor restroom walls, tenant demising walls.
|