FIR04-00063
| FIR-Aging Inspection | 10/28/2005 | 10/28/2005 | 10/31/2005 11:23:54 AM | | NR |
|
|
Greg is following up
|
BLD05-01608
| FIRE-Final Inspection | 10/27/2005 | 10/28/2005 | 10/28/2005 5:26:20 PM | P | CANC |
|
|
Not ready
|
FIR05-00601
| INSP-Sprinkler Rough-in/Hydro | 10/27/2005 | 10/28/2005 | 10/28/2005 3:09:51 PM | P | FAIL |
|
|
Piping as installed does not match plans. Wall layout does not match plans. Additional 90's and Tee's have been installed including in the remote area and piping has been rerouted. Heads have been deleted in restrooms but added in area immediately outside of the restrooms. Wall layout has changed. Resubmit updated plans for approvals.
|
FIR05-00597
| INSP-Sprinkler Rough-in/Hydro | 10/27/2005 | 10/28/2005 | 10/28/2005 3:09:23 PM | P | FAIL |
|
|
Piping as installed does not match plans. Wall layout does not match plans. Additional 90's and Tee's have been installed including in the remote area and piping has been rerouted. Heads have been deleted in restrooms but added in area immediately outside of the restrooms. Wall layout has changed. Resubmit updated plans for approvals.
|
FIR05-00506
| INSP-Sprinkler Rough-in/Hydro | 10/27/2005 | 10/28/2005 | 10/28/2005 2:24:45 PM | A | PASS |
|
|
Still need ceiling tile and canopies in some locations. Corrections as noted on plans corrected. Hydro test passed.
|
FIR05-00532
| INSP-Final Inspection | 10/26/2005 | 10/28/2005 | 10/28/2005 9:43:44 AM | A | PASS |
|
|
Fire alarm finaled
|
FIR05-00598
| INSP-Final Inspection | 10/20/2005 | 10/28/2005 | 10/28/2005 9:43:18 AM | A | FAIL |
|
|
Fire alarm is not ready
|
BLD05-01484
| FIRE-Final Inspection | 10/20/2005 | 10/28/2005 | 10/28/2005 9:42:53 AM | A | FAIL |
|
|
Fire alarm was not ready
|
FIR05-00556
| INSP-Final Inspection | 10/27/2005 | 10/28/2005 | 10/28/2005 8:20:03 AM | A | FAIL |
|
|
Left message on Jims phone. No body at job site.
|