Inspections for the day of: Friday, October 28, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00063 FIR-Aging Inspection10/28/200510/28/200510/31/2005 11:23:54 AM NR
Greg is following up
BLD05-01608 FIRE-Final Inspection10/27/200510/28/200510/28/2005 5:26:20 PMPCANC
Not ready
FIR05-00601 INSP-Sprinkler Rough-in/Hydro10/27/200510/28/200510/28/2005 3:09:51 PMPFAIL
Piping as installed does not match plans. Wall layout does not match plans. Additional 90's and Tee's have been installed including in the remote area and piping has been rerouted. Heads have been deleted in restrooms but added in area immediately outside of the restrooms. Wall layout has changed. Resubmit updated plans for approvals.
FIR05-00597 INSP-Sprinkler Rough-in/Hydro10/27/200510/28/200510/28/2005 3:09:23 PMPFAIL
Piping as installed does not match plans. Wall layout does not match plans. Additional 90's and Tee's have been installed including in the remote area and piping has been rerouted. Heads have been deleted in restrooms but added in area immediately outside of the restrooms. Wall layout has changed. Resubmit updated plans for approvals.
FIR05-00506 INSP-Sprinkler Rough-in/Hydro10/27/200510/28/200510/28/2005 2:24:45 PMAPASS
Still need ceiling tile and canopies in some locations. Corrections as noted on plans corrected. Hydro test passed.
FIR05-00532 INSP-Final Inspection10/26/200510/28/200510/28/2005 9:43:44 AMAPASS
Fire alarm finaled
FIR05-00598 INSP-Final Inspection10/20/200510/28/200510/28/2005 9:43:18 AMAFAIL
Fire alarm is not ready
BLD05-01484 FIRE-Final Inspection10/20/200510/28/200510/28/2005 9:42:53 AMAFAIL
Fire alarm was not ready
FIR05-00556 INSP-Final Inspection10/27/200510/28/200510/28/2005 8:20:03 AMAFAIL
Left message on Jims phone. No body at job site.