Inspections for the day of: Tuesday, October 28, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00072 INSP-Final Inspection10/28/200810/28/200810/30/2008 10:57:53 AMADONE
Scope of work completed by a different contractor.
FIR08-00239 INSP-Sprinkler Rough-in/Hydro10/27/200810/28/200810/28/2008 5:50:49 PMPPART
Building #3 2nd floor wet and dry system rough-in inspections passed with the exception of 5 concealed combustible attic pockets in need of sprinkler protection-or to be filled entirely with insulation per NFPA 13 exceptions including 2 pockets at the dry system, also noted one upright head to be relocated due to truss obstructions. See annotations on stamped plan set for locations.
FIR08-00715 INSP-Final Inspection10/28/200810/28/200810/28/2008 5:45:06 PMPPASS
Rough-in and final inspections completed at the same time, fire sprinkler permit finaled.
BLD06-02892 FIRE-Final Inspection10/27/200810/28/200810/28/2008 3:33:57 PMPPASS
C/N completed, gate hardware is acceptable, life safety inspection passed.
BLD07-03106 FIRE-Final Inspection10/27/200810/28/200810/28/2008 3:32:46 PMPFAIL
Provide missing max. occupant load signs, remove keyed locking deadbolt above the panic hardware at the second exit, install exit sign/EM light above the main door per approved plan. See fire code review notes items 7,8,9, and 12 for details.
BLD07-00337 FIRE-Conference10/28/200810/28/200810/28/2008 1:20:07 PMADONE
Scope of permit work is not yet completed for inspection at this time.
FIR08-00544 INSP-Sprinkler Rough-in/Hydro10/28/200810/28/200810/28/2008 1:19:05 PMAPART
OH system modifications approved as noted on plans to date.
BLD08-00572 FIRE-Final Inspection10/28/200810/28/200810/28/2008 1:17:56 PMAFAIL
Need project related fire sprinkler work completed prior to BLD permit final.