BLD10-01995
| FIRE-Final Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 4:51:31 PM | P | FAIL |
|
|
The address needs to face Maple Grove, single action hardware needs to be provided on the rear exit door (do not install deadbolt) and the gas closet needs the required venting as per IFC chapter 30 (vents were not within 6" of ceiling and floor.
|
BLD10-02279
| FIRE-Final Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 4:19:40 PM | P | PASS |
|
|
Life safety passed. The correct address will be posted with the tenant improvement permit.
|
FIR09-00109
| FIR-Aging Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 11:00:53 AM | | NR |
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR09-00095
| FIR-Aging Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 11:00:13 AM | | NR |
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR09-00084
| FIR-Aging Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 10:59:26 AM | | NR |
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR09-00107
| FIR-Aging Inspection | 10/28/2010 | 10/28/2010 | 10/28/2010 10:58:51 AM | | NR |
|
|
Work is in progress. Per Guy all of these AES inspections are being called in shortly.
|
FIR10-00442
| INSP-Final Inspection | 10/27/2010 | 10/28/2010 | 10/28/2010 10:24:56 AM | P | PASS |
|
|
permit finaled
|
BLD10-02086
| FIRE-Final Inspection | 10/27/2010 | 10/28/2010 | 10/28/2010 10:17:03 AM | A | FAIL |
|
|
See the city approved plans for redlines on items that need corrected which include overspaced/missing sprinkler heads, inoperative exit signs/emergency lights, incorrect door hardware and I need verification that the access controlled egress doors are connected to the fire alarm system.
|