Inspections for the day of: Wednesday, October 28, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02665 ELE-Aging Inspection10/28/201510/28/201510/28/2015 4:40:34 PM DONE
called contractor
ELE12-02665 Final10/28/201510/28/201510/28/2015 4:40:02 PMPPASS
Called contractor informed UL listing no longer required for industrial equipment due to law that passed. Final ok
ELE15-01111 Final10/26/201510/28/201510/28/2015 4:31:35 PMPPART
WE need a Final Temp occupancy, please. If you have any questions, please contact Danny at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Still need west showroom outlets, rt bath off lounge, roof, riser rm, compressor/oil storage room, quick lube, car wash, receptacle outlet with in 50' of service, parking lot recepts, additional parking area yet to finish. Offices and lounge areas ok occupy
ELE15-00338 Electrical Rough-In10/28/201510/28/201510/28/2015 2:50:15 PMPFAIL
Butch Phone #: ###-####
210.63- A 120 volt 15 or 20 amp receptacle outlet shall be located with in 25' of HVAC units outside east and west.
210.64- A 120 volt 15 or 20 amp receptacle outlet shall be located with in 50' of electrical service equipment.
300.15- MC cable shall terminate in a box by middle door.
314.22- Surface extension or mudring shall be installed on box west wall switch.
HVAC-AC disconnecting means shall be located at least 2' measured horizonally from gas meter vent.
ELE15-03466 Electrical Rough-In10/27/201510/28/201510/28/2015 2:05:01 PMPPASS
Rough inspect of walls and ceiling areas. Contact is Matt Malloy. Phone #: ###-#### Inspection requested via web by Richard Montgomery Repair area to be ventilated as per 511.3(C)(1)a- 4 air exchanges per hour with vent ducts to be installed with in 12" of floor. All walls and ceilings rough in ok cover.
ELE13-03383 Final10/28/201510/28/201510/28/2015 1:38:09 PMPPASS
Contractor asked me to final permit. Did not perform any work under this permit work completed under permit ele13-03248. Final ok
ELE15-03475 Electrical Rough-In10/27/201510/28/201510/28/2015 1:20:30 PMAFAIL
Contact is Mike ###-#### Phone #: ###-#### Inspection requested via web by Clint Tate 210.11(C)(2)- 120 volt 20 amp laundry circuit shall have no other outlets.
250.53(A)(2)- Where water bond has been removed supplemental grounding electrode required. A single ground rod shall be supplemented by additional rod.
ELE15-02850 Final10/26/201510/28/201510/28/2015 12:52:44 PMPPASS
Please call Jennifer when you are on your way, ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE15-03472 Electrical Rough-In10/27/201510/28/201510/28/2015 12:20:03 PMAPASS
If you have any questions, please call Jeff ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan North wall repair rough in ok cover
ELE15-03422 Electrical Rough-In10/27/201510/28/201510/28/2015 11:36:13 AMAPASS
Underground inspection for conduit
Contact Travis at ###-#### Phone #: ###-#### Inspection requested via web by Cathy Duchek Underground 18" down with additional 18" to back fill. Underground N.E. lot for 8 light poles rough in ok cover
ELE15-03424 Final10/27/201510/28/201510/28/2015 11:04:57 AMAPASS
We are requesting a final inspection for tomorrow 10/28/15 in the afternoon. Our contact is Trent @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate Acual space 2150. Final ok
ELE15-02800 Final10/27/201510/28/201510/28/2015 10:34:26 AMAPASS
The access code is 6949, any questions plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren Final ok
ELE15-02684 Final10/27/201510/28/201510/28/2015 10:13:21 AMAPASS
Please contact Tracy ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Tracy Robertson Final ok
ELE15-02696 Electrical Rough-In10/27/201510/28/201510/28/2015 9:44:46 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
110.14- All unused openings shall be closed. 1/2" KO seals needed.
300.11- All luminaires shall be supported independant of grid.
300.15- MC cable shall terminate in a box.
All near offices with open walls.
ELE15-02837 Final10/28/201510/28/201510/28/2015 8:45:03 AMAPASS
CODE 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE15-03424 Electrical Rough-In10/27/201510/28/201510/27/2015 2:37:30 PMAPASS
Rough inspection Phone #: ###-#### Inspection requested via web by Clint Tate Receptacles fished down walls. grid rough in ok cover