Inspections for the day of: Wednesday, October 28, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00743 INSP-Final Inspection10/28/201510/28/201510/29/2015 8:47:47 AMPPASS
permit finaled
BLD15-01535 FIRE-Final Inspection10/26/201510/28/201510/28/2015 4:17:35 PMAFAIL
Per plan review the sensor shall be installed for door release. All other items ok
BLD05-01282 FIRE-Conference10/22/201510/28/201510/28/2015 2:24:44 PMADONE
I received a phone call from Brian with Local Alarm inquiring about what is needed. I set up another conference for next week to follow up.
BLD15-02792 FIRE-Final Inspection10/28/201510/28/201510/28/2015 12:50:55 PMPPASS
Life safety passed
FIR15-00582 INSP-Sprinkler Rough-in10/28/201510/28/201510/28/2015 12:45:19 PMPPASS
Rough-in passed. Piping can be covered.
FIR15-00743 INSP-Sprinkler Rough-in10/28/201510/28/201510/28/2015 12:40:28 PMPPASS
Rough-in passed.
BLD15-03858 FIRE-Conference10/28/201510/28/201510/28/2015 11:35:52 AMPDONE
Ok to cover sprinkler head in walled off dead space. We discussed the need for a sprinkler permit to address the three pendants that are located too close to one another.
FIR15-00714 INSP-Sprinkler Rough-in10/27/201510/28/201510/28/2015 11:11:56 AMAFAIL
Pipe is not at the minimum 4'-6" bury
FIR15-00713 INSP-Sprinkler Rough-in10/27/201510/28/201510/28/2015 11:10:58 AMAFAIL
Pipe is not at the minimum 4'-6" bury
BLD13-02351 FIRE-Final Inspection10/27/201510/28/201510/28/2015 11:08:51 AMAPASS
life safety passed
FIR15-00717 INSP-Sprinkler Rough-in10/27/201510/28/201510/28/2015 10:08:07 AMADONE
United water installed the short run of underground supply to riser room. Was not inspected by myself or the sprinkler contractor.
FIR15-00379 INSP-Final Inspection10/28/201510/28/201510/28/2015 10:06:31 AMAPASS
Permit finaled