FIR15-00743
| INSP-Final Inspection | 10/28/2015 | 10/28/2015 | 10/29/2015 8:47:47 AM | P | PASS |
|
|
permit finaled
|
BLD15-01535
| FIRE-Final Inspection | 10/26/2015 | 10/28/2015 | 10/28/2015 4:17:35 PM | A | FAIL |
|
|
Per plan review the sensor shall be installed for door release. All other items ok
|
BLD05-01282
| FIRE-Conference | 10/22/2015 | 10/28/2015 | 10/28/2015 2:24:44 PM | A | DONE |
|
|
I received a phone call from Brian with Local Alarm inquiring about what is needed. I set up another conference for next week to follow up.
|
BLD15-02792
| FIRE-Final Inspection | 10/28/2015 | 10/28/2015 | 10/28/2015 12:50:55 PM | P | PASS |
|
|
Life safety passed
|
FIR15-00582
| INSP-Sprinkler Rough-in | 10/28/2015 | 10/28/2015 | 10/28/2015 12:45:19 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR15-00743
| INSP-Sprinkler Rough-in | 10/28/2015 | 10/28/2015 | 10/28/2015 12:40:28 PM | P | PASS |
|
|
Rough-in passed.
|
BLD15-03858
| FIRE-Conference | 10/28/2015 | 10/28/2015 | 10/28/2015 11:35:52 AM | P | DONE |
|
|
Ok to cover sprinkler head in walled off dead space. We discussed the need for a sprinkler permit to address the three pendants that are located too close to one another.
|
FIR15-00714
| INSP-Sprinkler Rough-in | 10/27/2015 | 10/28/2015 | 10/28/2015 11:11:56 AM | A | FAIL |
|
|
Pipe is not at the minimum 4'-6" bury
|
FIR15-00713
| INSP-Sprinkler Rough-in | 10/27/2015 | 10/28/2015 | 10/28/2015 11:10:58 AM | A | FAIL |
|
|
Pipe is not at the minimum 4'-6" bury
|
BLD13-02351
| FIRE-Final Inspection | 10/27/2015 | 10/28/2015 | 10/28/2015 11:08:51 AM | A | PASS |
|
|
life safety passed
|
FIR15-00717
| INSP-Sprinkler Rough-in | 10/27/2015 | 10/28/2015 | 10/28/2015 10:08:07 AM | A | DONE |
|
|
United water installed the short run of underground supply to riser room. Was not inspected by myself or the sprinkler contractor.
|
FIR15-00379
| INSP-Final Inspection | 10/28/2015 | 10/28/2015 | 10/28/2015 10:06:31 AM | A | PASS |
|
|
Permit finaled
|