Inspections for the day of: Wednesday, October 28, 2015.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00750 INSP-Sprinkler Rough-in10/27/201510/28/201510/28/2015 12:26:37 PMAPART
Started 24 hour air test of dry pipe fire sprinkler system for Bldg. K. Will reinspect tomorrow same time (9:00am) to confirm holding after 24 hours.
FIR15-00329 INSP-Supply line flush10/27/201510/28/201510/28/2015 12:24:16 PMAFAIL
Rough inspection of fire service underground supply line (south side) into convention center portion of the building. U/G supply line penetrates building foundation without proper clearanace. Contractor agreed to remove pipe as needed to provide a clearance sleeve (10") around the 6" supply line.