ELE17-03557
| ELE-Aging Inspection | 10/28/2019 | 10/28/2019 | 11/1/2019 2:19:37 PM | | FAIL |
|
|
Drove by to check if ok to final. 110.24- Available fault current shall be posted with date calculated as noted on permanent service inspection.
|
ELE19-03536
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 3:43:54 PM | P | PASS |
|
|
Call 30 minutes in advance if possible; Phone #: ###-#### Inspection requested via web by Steve McCloy Final ok
|
ELE19-03536
| Electrical Rough-In | 10/28/2019 | 10/28/2019 | 10/28/2019 3:29:42 PM | P | PASS |
|
|
Call 30 minutes in advance if possible; Phone #: ###-#### Inspection requested via web by Steve McCloy All items fished in. Only motion sensor located in new walls. Rough in ok.
|
ELE19-03756
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 3:11:21 PM | P | NH |
|
|
Call Mike if needed Phone #: ###-#### Inspection requested via web by Rob Maes No answer at door. Inspectors are not allowed to trespass on personal property without either owner home or rep from complany contracted to due work. Recall when someone available for access.
|
ELE19-03008
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 2:32:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
ELE19-02744
| Final | 10/28/2019 | 10/28/2019 | 10/28/2019 2:00:34 PM | P | FAIL |
|
|
Final / Trim Out. Please call half hour ahead of time Todd ###-#### He will meet you on site. Phone #: ###-#### Inspection requested via web by Kendra Lanham 334.12- NM cable shall not be installed in a damp location like interior of a conduit on exterior of structure. 3 branch circuit conduits from service to under addition. 352.30- PVC service riser shall be secured with in 3' of meter/panel combo. * 9-3-19 a rough in inspection had been requested. Inspector arrived but did not have access due to no one home. Job proceded with out electrical inspection being performed. With a licensed and insured electrical contractor performing electrical work no removal of wall cover needed.
|
ELE19-04142
| Rough-In Permanent Service | 10/28/2019 | 10/28/2019 | 10/28/2019 1:30:59 PM | P | PASS |
|
|
rough-in cover for service in shed. electrician Duke not onsite, ###-####. can call office for more details. Phone #: ###-#### Inspection requested via web by Matthew White 200 amp overhead service on 348 sq. ft. shed. Shed to have complete wall cover. Rough in ok cover p/s o/h n ok
|
ELE19-04026
| Final | 10/25/2019 | 10/28/2019 | 10/28/2019 11:59:56 AM | A | PASS |
|
|
We will call and schedule a time to meet you onsite Phone #: ###-#### Inspection requested via web by Jesse Simpson Final ok
|
ELE19-03994
| Final | 10/25/2019 | 10/28/2019 | 10/28/2019 11:59:19 AM | A | PASS |
|
|
Final electrical and service inspection in conjunction with AltEnergy final solar inspection.
Thank you ; have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL No changes made on load side of service. Final ok
|
ELE19-03360
| Final | 10/25/2019 | 10/28/2019 | 10/28/2019 10:59:49 AM | A | PASS |
|
|
On Site Contact is Mierins Rozentals Phone #: ###-#### Inspection requested via web by BRS Permitting Final ok
|
ELE19-04039
| Rough-In Permanent Service | 10/28/2019 | 10/28/2019 | 10/28/2019 10:33:00 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Attic boxes trimmed at rough in. Rough in ok cover p/s u/g n ok
|
ELE19-02648
| Final | 10/25/2019 | 10/28/2019 | 10/28/2019 10:05:27 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins Corrections not complete. Unable to final due to plan modification is under review. 210.8(B)- All 120 volt 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. Dishwasher, refrigerator. Called and had ELE attached to BLD19-02257.
|
ELE19-03876
| Electrical Rough-In | 10/25/2019 | 10/28/2019 | 10/28/2019 9:19:24 AM | A | PART |
|
|
Partial rough-in. Phone #: ###-#### Inspection requested via web by Bryan Atkins BCC 4-05-23- Reminded contractor it is unlawful to cover in any way electrical wiring or equipment without first having same inspected by an electrical inspector. General contractor pressuring to cover ready or not. HR chase and 4'x4' upper corners around room for soffit construction rough in ok cover.
|