FIR01-00330
| FIR-Aging Inspection | 10/29/2001 | 10/29/2001 | 10/29/2001 12:00:00 AM | | NH |
|
|
Visited job site system is in. I notified contractor that inspection is needed. 10/29/2001 4:04:50 PM
|
FIR01-00385
| INSP-Sprinkler Rough-in/Hydro | 10/29/2001 | 10/29/2001 | 10/29/2001 12:00:00 AM | P | FAIL |
|
|
Added by Inspector: 430 On 10/29/2001 4:03:57 PM Existing Area- 12' max storage heights exceeded. Need 4 way EQ brace in storage and show rooms. Need to center heads under all doors. In existing repair area heads to far from bottom of joistes and pipe hits garage door.Acc. area sidewall and pendant heads to far from walls. Attic area above lounge, heads overspaced. Mech unit in attic blocks head. Repair tenting in attic.
|