Inspections for the day of: Monday, October 29, 2001.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00330 FIR-Aging Inspection10/29/200110/29/200110/29/2001 12:00:00 AM NH
Visited job site system is in. I notified contractor that inspection is needed. 10/29/2001 4:04:50 PM
FIR01-00385 INSP-Sprinkler Rough-in/Hydro10/29/200110/29/200110/29/2001 12:00:00 AMPFAIL
Added by Inspector: 430 On 10/29/2001 4:03:57 PM Existing Area- 12' max storage heights exceeded. Need 4 way EQ brace in storage and show rooms. Need to center heads under all doors. In existing repair area heads to far from bottom of joistes and pipe hits garage door.Acc. area sidewall and pendant heads to far from walls. Attic area above lounge, heads overspaced. Mech unit in attic blocks head. Repair tenting in attic.