Inspections for the day of: Friday, October 29, 2004.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS04-00272 FIR-Final9/29/200410/29/200410/29/2004 12:00:00 AMANR
verify FD access roads, hydrants, and location of foundation as shown on plans for FD accessibility. Structures are to be temporary only. Talked to Matt (###-####) and they plan to start this project at the end of Nov or early Dec; rescheduled for 11/30 10/29/2004 11:58:23 AM
FIR04-00595 INSP-Final Inspection10/28/200410/29/200410/29/2004 12:00:00 AMAFAIL
Steve; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner Janitor closet lacking sprinkler protection; heads overspaced (130 sq ft) in middle of sales floor as design is 120 sq ft; need spare heads in head box 10/29/2004 10:56:00 AM
BLD03-02173 FIRE-Final Inspection10/28/200410/29/200410/29/2004 12:00:00 AMAPART
Ron; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner Per Dave Miller temp occupancy approved pending fire lane curbs painted 10/29/2004 4:40:46 PM
FIR04-00217 INSP-Alarm Testing10/28/200410/29/200410/29/2004 12:00:00 AMPPASS
Cell Phone ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR04-00382 INSP-Alarm Testing10/28/200410/29/200410/29/2004 12:00:00 AMPFAIL
Cell Phone ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino Need to verify ceiling mount strobe used is listed for ceiling 10/29/2004 2:40:07 PM
FIR04-00263 INSP-Final Inspection10/28/200410/29/200410/29/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/28/2004 at 1:15:43 PM. Contact: ###-####.
BLD04-01860 FIRE-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPART
Jim; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner Per Dave Miller temp occupancy approved pending completion of fire alarm permit 10/29/2004 4:19:35 PM
BLD04-01071 FIRE-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
Mark call before you go out; Phone #: ###-#### Internet Inspection Request from: Jan Rice
FIR04-00208 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 10/29/2004 at 10:29:55 AM. Contact: ###-####.
FIR04-00504 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPCANC
Final Inspection - Contact Matt; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Per Jim Danes this will be rescheduled 10/29/2004 4:31:34 PM
FIR04-00579 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPFAIL
Jim ###-#### Sprinkler bell activates on any alarm; need to complete 2 duct detectors in book warehouse 10/29/2004 4:17:38 PM
FIR04-00263 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
BLD04-00697 FIRE-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
FIR04-00567 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
FIR04-00595 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
FIR04-00514 INSP-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMPPASS