Inspections for the day of: Friday, October 29, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00236 INSP-Final Inspection10/27/200410/29/200410/29/2004 12:00:00 AMACANC
Wrong permit called in for hydro test. See underground supply line permit for entry. 10/29/2004 2:28:59 PM
FIR04-00592 INSP-Sprinkler Rough-in10/28/200410/29/200410/29/2004 12:00:00 AMAPART
Inspection was for overhead sprinkler roughing and tenting. Overhead sprinklers are ok to cover. Underground supply piping is ok except for the water meter is not the right size. Its 3/4" not 1" as required. 10/29/2004 1:59:13 PM
BLD03-02332 FIRE-Final Inspection10/28/200410/29/200410/29/2004 12:00:00 AMAPASS
Fire life safety finaled 10/29/2004 3:48:07 PM
BLD04-00963 FIRE-Final Inspection10/29/200410/29/200410/29/2004 12:00:00 AMAPASS
Fire life safety finaled 10/29/2004 3:48:24 PM
FIR04-00164 INSP-Sprinkler Rough-in/Hydro10/29/200410/29/200410/29/2004 12:00:00 AMPPASS
Underground supply line hydro test passed