ELE08-02922
| Rough-In Permanent Service | 10/29/2008 | 10/29/2008 | 10/29/2008 3:30:23 PM | P | FAIL |
|
|
###-#### Internet Inspection Request from: Todd Holbrook called corr. and do not cover posted 250.148 j box in closet splice equip grds together, 300.4 nail plates and 11/4" grd pancake box M bath 110.12(A) seal KOs back of meterbase and jbox, 250.52(A)(1) or 104 (A)(1) grd or bond water to p/s remove GEC from jbox and shall not splice it, 334.30 staple cables within 12" of metal boxes shall update permit for 6 rms
|
ESC08-00780
| General Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 3:29:51 PM | P | PASS |
|
|
trash cleaned up and in trailer site ok
|
ELE08-02503
| Final | 10/29/2008 | 10/29/2008 | 10/29/2008 2:43:48 PM | P | PASS |
|
|
This is ready for a final anytime today Phone #: ###-#### Internet Inspection Request from: Don Lustig card signed ok
|
ELE08-02924
| Final | 10/29/2008 | 10/29/2008 | 10/29/2008 1:57:01 PM | P | FAIL |
|
|
tim Phone #: ###-#### no access
|
ELE08-02477
| Final | 10/29/2008 | 10/29/2008 | 10/29/2008 1:39:44 PM | P | PASS |
|
|
allen Phone #: ###-#### ok
|
ELE08-02476
| Final | 10/29/2008 | 10/29/2008 | 10/29/2008 1:39:27 PM | P | PASS |
|
|
allen Phone #: ###-#### ok
|
ELE08-01419
| Final | 10/29/2008 | 10/29/2008 | 10/29/2008 12:29:52 PM | P | PASS |
|
|
equip tested and labeled field evaluation ok
|
ELE08-01015
| ELE-Aging Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 11:01:53 AM | | PART |
|
|
wsuc
|
ELE08-00655
| ELE-Aging Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 11:01:35 AM | | PART |
|
|
was at site 10-28-08
|
ELE07-03432
| ELE-Aging Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 10:21:07 AM | | PART |
|
|
wsuc
|
ESC08-00844
| General Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 10:07:51 AM | A | PASS |
|
|
ok
|
ELE08-02791
| Final | 10/28/2008 | 10/29/2008 | 10/29/2008 10:07:13 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jenni Keller ok
|
ELE07-02822
| DOC - Permit Expired | 10/29/2008 | 10/29/2008 | 10/29/2008 9:43:19 AM | A | PASS |
|
|
job taken oven different contr under new permit
|
ELE08-02917
| Final | 10/28/2008 | 10/29/2008 | 10/29/2008 9:41:39 AM | A | PASS |
|
|
tom Phone #: ###-#### ok
|
ELE08-02662
| Electrical Rough-In | 10/29/2008 | 10/29/2008 | 10/29/2008 8:49:59 AM | A | CANC |
|
|
|
ELE08-02662
| Final | 10/28/2008 | 10/29/2008 | 10/29/2008 8:49:43 AM | A | CANC |
|
|
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten called ele not attached to bld
|
ELE08-02604
| Final | 10/28/2008 | 10/29/2008 | 10/29/2008 8:10:10 AM | A | PASS |
|
|
Final Electrical Inspection- Please call James @ ###-#### to meet Phone #: ###-#### Internet Inspection Request from: Beka Hereau ok card signed
|
ESC08-00651
| General Inspection | 10/29/2008 | 10/29/2008 | 10/29/2008 8:09:46 AM | A | PASS |
|
|
ok
|