Inspections for the day of: Tuesday, October 29, 2013.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02254 ELE-Aging Inspection10/29/201310/29/201310/31/2013 11:05:30 AM DONE
still under construction
ELE10-02099 ELE-Aging Inspection10/29/201310/29/201310/31/2013 11:04:23 AM DONE
still under construction
ELE12-00736 ELE-Aging Inspection10/29/201310/29/201310/31/2013 11:03:12 AM DONE
still under construction
ELE09-02232 ELE-Aging Inspection10/29/201310/29/201310/31/2013 11:01:52 AM DONE
waiting for contractor to call
ELE13-01462 Final10/28/201310/29/201310/29/2013 3:24:46 PMPCANC
Try to give me an hour notice so I can meet you there Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, wants to re-schedule
ELE13-03009 Electrical Rough-In10/29/201310/29/201310/29/2013 3:23:46 PMPPASS
H2O Environmental. Lighting retrofit highbays Phone #: ###-#### >> Inspection requested via web by Tim Dunlop ri ok
ELE13-02707 Rough-In Permanent Service10/29/201310/29/201310/29/2013 2:44:14 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE13-02968 Electrical Rough-In10/28/201310/29/201310/29/2013 1:53:16 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called to change room count to 18 rooms, ri ok, will call for service later
ELE13-02435 Final10/29/201310/29/201310/29/2013 1:16:08 PMAPASS
Garage entrance code 1979E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
ELE13-02323 Electrical Rough-In10/29/201310/29/201310/29/2013 12:32:20 PMPFAIL
rough cover second level stair wells Phone #: ###-#### >> Inspection requested via web by fred lopez called, common area wiring shall be in mc cable
ELE13-03011 Final10/29/201310/29/201310/29/2013 10:39:15 AMPCANC
address is Suite # 103 Phone #: ###-#### >> Inspection requested via web by David McClellan see ri
ELE13-02993 Permanent Service10/29/201310/29/201310/29/2013 10:33:37 AMAFAIL
Uffer inspection Phone #: ###-#### >> Inspection requested via web by Emmet Bushman called, concrete shall be clean, conductor shall be visible, there shall not be mud in area to be poured
ELE13-03011 Electrical Rough-In10/29/201310/29/201310/29/2013 9:59:03 AMAFAIL
address is Suite # 103 Phone #: ###-#### >> Inspection requested via web by David McClellan called, left correction notice, NEC 110.26 shall provide work space about electrical equipment, 300.14 shall provide 6" free conductor length at switch box
ELE13-02695 Electrical Rough-In10/28/201310/29/201310/29/2013 9:52:14 AMAPASS
james Phone #: ###-#### potting only ok
ELE13-03005 Permanent Service10/28/201310/29/201310/29/2013 9:20:34 AMAPASS
Need a permanant service so idaho power can hook up. Phone #: ###-#### >> Inspection requested via web by John Edwards called, new service at se corner building, p/s o/h rec ok
ELE13-02633 Electrical Rough-In10/28/201310/29/201310/29/2013 9:05:25 AMAPASS
reinspect for ceiling cover
Phone #: ###-#### >> Inspection requested via web by Don Lustig corrections made, main room and office ceilings ok cover
ELE13-02555 Final10/28/201310/29/201310/29/2013 8:31:19 AMAFAIL
garage code 9045 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 406.8(B) outside receptacles shall be listed weather resistant type, 210.8(A)(3) outdoor receptacles shall be GFCI type