ELE10-02254
| ELE-Aging Inspection | 10/29/2013 | 10/29/2013 | 10/31/2013 11:05:30 AM | | DONE |
|
|
still under construction
|
ELE10-02099
| ELE-Aging Inspection | 10/29/2013 | 10/29/2013 | 10/31/2013 11:04:23 AM | | DONE |
|
|
still under construction
|
ELE12-00736
| ELE-Aging Inspection | 10/29/2013 | 10/29/2013 | 10/31/2013 11:03:12 AM | | DONE |
|
|
still under construction
|
ELE09-02232
| ELE-Aging Inspection | 10/29/2013 | 10/29/2013 | 10/31/2013 11:01:52 AM | | DONE |
|
|
waiting for contractor to call
|
ELE13-01462
| Final | 10/28/2013 | 10/29/2013 | 10/29/2013 3:24:46 PM | P | CANC |
|
|
Try to give me an hour notice so I can meet you there Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, wants to re-schedule
|
ELE13-03009
| Electrical Rough-In | 10/29/2013 | 10/29/2013 | 10/29/2013 3:23:46 PM | P | PASS |
|
|
H2O Environmental. Lighting retrofit highbays Phone #: ###-#### >> Inspection requested via web by Tim Dunlop ri ok
|
ELE13-02707
| Rough-In Permanent Service | 10/29/2013 | 10/29/2013 | 10/29/2013 2:44:14 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE13-02968
| Electrical Rough-In | 10/28/2013 | 10/29/2013 | 10/29/2013 1:53:16 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Rhonda Zamagni called to change room count to 18 rooms, ri ok, will call for service later
|
ELE13-02435
| Final | 10/29/2013 | 10/29/2013 | 10/29/2013 1:16:08 PM | A | PASS |
|
|
Garage entrance code 1979E. Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
|
ELE13-02323
| Electrical Rough-In | 10/29/2013 | 10/29/2013 | 10/29/2013 12:32:20 PM | P | FAIL |
|
|
rough cover second level stair wells Phone #: ###-#### >> Inspection requested via web by fred lopez called, common area wiring shall be in mc cable
|
ELE13-03011
| Final | 10/29/2013 | 10/29/2013 | 10/29/2013 10:39:15 AM | P | CANC |
|
|
address is Suite # 103 Phone #: ###-#### >> Inspection requested via web by David McClellan see ri
|
ELE13-02993
| Permanent Service | 10/29/2013 | 10/29/2013 | 10/29/2013 10:33:37 AM | A | FAIL |
|
|
Uffer inspection Phone #: ###-#### >> Inspection requested via web by Emmet Bushman called, concrete shall be clean, conductor shall be visible, there shall not be mud in area to be poured
|
ELE13-03011
| Electrical Rough-In | 10/29/2013 | 10/29/2013 | 10/29/2013 9:59:03 AM | A | FAIL |
|
|
address is Suite # 103 Phone #: ###-#### >> Inspection requested via web by David McClellan called, left correction notice, NEC 110.26 shall provide work space about electrical equipment, 300.14 shall provide 6" free conductor length at switch box
|
ELE13-02695
| Electrical Rough-In | 10/28/2013 | 10/29/2013 | 10/29/2013 9:52:14 AM | A | PASS |
|
|
james Phone #: ###-#### potting only ok
|
ELE13-03005
| Permanent Service | 10/28/2013 | 10/29/2013 | 10/29/2013 9:20:34 AM | A | PASS |
|
|
Need a permanant service so idaho power can hook up. Phone #: ###-#### >> Inspection requested via web by John Edwards called, new service at se corner building, p/s o/h rec ok
|
ELE13-02633
| Electrical Rough-In | 10/28/2013 | 10/29/2013 | 10/29/2013 9:05:25 AM | A | PASS |
|
|
reinspect for ceiling cover Phone #: ###-#### >> Inspection requested via web by Don Lustig corrections made, main room and office ceilings ok cover
|
ELE13-02555
| Final | 10/28/2013 | 10/29/2013 | 10/29/2013 8:31:19 AM | A | FAIL |
|
|
garage code 9045 Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 406.8(B) outside receptacles shall be listed weather resistant type, 210.8(A)(3) outdoor receptacles shall be GFCI type
|